2.9 L: Protection Functions
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Fault
GF
Ground Fault
LF
Output Phase Loss
oC
Overcurrent
oH1
Heatsink Overheat
oL1
Motor Overload
oL2
Drive Overload
oL3
Overtorque Detection 1
oL4
Overtorque Detection 2
*1
Uv1 is the target for the auto restart process when L2-01 = 1, 2, 3, or 4 [Power Loss Ride Through Select = Enabled for L2-02 Time,
Enabled while CPU Power Active, Kinetic Energy Backup: L2-02, or Kinetic Energy Backup: CPU Power].
L5-01: Number of Auto-Restart Attempts
No.
Name
(Hex.)
L5-01
Number of Auto-Restart
Attempts
(049E)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
• The drive operates correctly for 10 minutes after a fault restart.
• When you manually clear a fault after the drive triggers protective functions.
• When you re-energize the drive.
L5-02: Fault Contact at Restart Select
No.
Name
(Hex.)
L5-02
Fault Contact at Restart
Select
(049F)
0 : Active Only when Not Restarting
1 : Always Active
L5-03: Continuous Method Max Restart T
No.
Name
(Hex.)
L5-03
Continuous Method Max
Restart T
(04A0)
L5-04: Interval Method Restart Time
No.
Name
(Hex.)
L5-04
Interval Method Restart
Time
(046C)
464
Table 2.69 List of Faults during which Auto Restart is Available
Parameters to Disable
Name
Auto Restart
L5-08
-
-
L5-08
L5-07
L5-07
L5-07
L5-07
V/f
CL-V/f
OLV
CLV
Sets the number of times that the drive will try to restart.
V/f
CL-V/f
OLV
CLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while the drive
is automatically restarting.
V/f
CL-V/f
OLV
CLV
Sets the time for which the drive will try to restart. If the drive cannot restart inthe time set in L5-03,
the drive detects a fault. This is available when L5-05 = 0 [Auto-Restart Method = Continuous/
Immediate Attempts].
V/f
CL-V/f
OLV
CLV
Sets the time interval between each Auto Restart attempt. This function is enabled when L5-05 = 1
[Auto Restart Operation Selection = Use L5-04 Time].
Fault
ov
Overvoltage
PF
Input Phase Loss
rH
Braking Resistor Overheat
rr
Dynamic Braking Transistor
Fault
STPo
Motor Step-Out Detected
Uv1
DC Bus Undervoltage
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Parameters to Disable
Name
Auto Restart
L5-08
-
-
-
-
*1
L5-08
Default
(Range)
0
(0 - 10 times)
Default
(Range)
0
(0, 1)
Default
(Range)
10.0 s
(0.5 - 180.0 s)
Default
(Range)
10.0 s
(0.5 - 600.0 s)