2.3 b: Application
Set Speed Search to H1-xx to do the function externally. You cannot set external Speed Search 1 and 2 at the same
time.
H1-xx Setting
61
Speed Search from Fmax
62
Speed Search from Fref
• Do Speed Search with Each Auto Restart
Set L5-01 [Number of Auto-Restart Attempts] = 1 or more. After there is an Auto Restart fault, the drive
automatically does Speed Search.
• Do Speed Search after Momentary Power Loss
Set L2-01 =1, 2 [Power Loss Ride Through Select = Enabled for L2-02 Time, Enabled while CPU Power Active].
• Do Speed Search after You Clear the External Baseblock Command
After you clear the external baseblock command, enable the Run command, and when the output frequency is
higher than the minimum frequency, the drive does Speed Search.
b3-01: Speed Search at Start Selection
No.
Name
(Hex.)
b3-01
Speed Search at Start
Selection
(0191)
0 : Disabled
Enter a Run command to start to operate the drive at the minimum output frequency.
When the Run command is enabled and the Speed Search from Fmax or Fref [H1-xx = 61, 62] is input from a multi-
function input terminal, the drive will do Speed Search and start to operate the motor.
1 : Enabled
Enter the Run command to do Speed Search. The drive completes Speed Search then starts to operate the motor.
b3-02: SpeedSearch Deactivation Current
No.
Name
(Hex.)
b3-02
SpeedSearch Deactivation
Current
(0192)
If the drive cannot restart the motor, decrease this setting.
b3-03: Speed Search Deceleration Time
No.
Name
(Hex.)
b3-03
Speed Search Deceleration
Time
(0193)
This is the output frequency deceleration time used by Current Detection Speed Search and by the Current Injection
Method of Speed Estimation Speed Search.
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this parameter takes effect only in Expert Mode.
• If the drive detects oL1 [Motor Overload] during Current Detection Speed Search, decrease the value set in b3-03.
214
Table 2.23 Execute Speed Search via the Digital Input Terminals
Name
ON: Speed Search starts from E1-04 [Maximum Output
Frequency].
ON: Speed Search starts from the frequency reference
immediately before you input the Speed Search
command.
V/f
CL-V/f
OLV
Sets the Speed Search at Start function where the drive will perform Speed Search with each Run
command.
V/f
CL-V/f
OLV
Sets the current level that stops Speed Search as a percentage of the drive rated output current.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
Sets the deceleration time during Speed Search operation. Set the length of time to decelerate from
the maximum output frequency to the minimum output frequency.
Current Detection 2
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Speed Estimation
External Speed Search commands 1 and 2 work the
same.
The drive estimates the motor speed, then starts Speed
Search from the estimated speed.
Default
(Range)
Determined by A1-02
Default
(Range)
Determined by A1-02
(0 - 200%)
Default
(Range)
(0.1 - 10.0 s)
(0, 1)
2.0 s

Advertisement

Table of Contents
loading

Table of Contents