YASKAWA GA800 Programming Manual page 86

Ac drive for industrial applications
Table of Contents

Advertisement

1.11 L: Protection Functions
No.
Name
(Hex.)
L5-04
Interval Method Restart
Time
(046C)
L5-05
Auto-Restart Method
(0467)
L5-07
Fault Reset Enable Select
Grp1
(0B2A)
L5-08
Fault Reset Enable Select
Grp2
(0B2B)
86
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time interval between each Auto Restart attempt. This function is enabled when
L5-05 = 1 [Auto Restart Operation Selection = Use L5-04 Time].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the count method for the Auto Restart operation.
0 : Continuous/Immediate Attempts
1 : Interval/Attempt after L5-04 sec
V/f
CL-V/f
OLV
CLV
AOLV
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the
digits set oL1, oL2, oL3, and oL4, in order.
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
V/f
CL-V/f
OLV
CLV
AOLV
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to
right, the digits set Uv1, ov, oH1, and GF, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
Ref.
(Range)
10.0 s
464
(0.5 - 600.0 s)
0
465
(0, 1)
1111
465
(0000 - 1111)
1111
465
(0000 - 1111)

Advertisement

Table of Contents
loading