YASKAWA GA800 Programming Manual page 337

Ac drive for industrial applications
Table of Contents

Advertisement

F6-16
[Gateway Mode]
Drive 0
*2
1 - 4
(Master Drive)
Drive 1
0
(Slave drive)
Drive 2
0
(Slave drive)
Drive 3
0
(Slave drive)
Drive 4
0
(Slave drive)
*1
Restart the drive to apply the new settings.
*2
Specify the number of slave drives you will connect.
*3
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
*4
Set a slave address that is different from other slave devices.
*5
Enter the same value that you use for the master drive.
*6
To correctly detect the response timeout, do not change the value of H5-06 from the default value.
*7
Set H5-09 ≥ 0.9. When H5-09 < 0.9, the drive will detect CE [Modbus Communication Error] before it detects a response timeout.
*8
On each slave drive, set b1-01 [Frequency Reference Selection 1] and b1-02 [Run Command Selection 1] to 2 [Memobus/Modbus
Communications].
An Overview of Gateway Mode
When in gateway mode, the drive operates as shown in
A - Controller
B - Communication Option
Controller to Communication Option Card
• The controller and card communicate in the format of
each field bus communications protocol.
• Drive 0 sends commands and monitors through normal
field bus communications.
• The special registers of Drive 0 use read and write to
send commands to and monitor Drives 1 to 4.
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Table 2.50 Sample Settings for Using Gateway Mode
H5-02
[Communication
H5-01
Speed Selection]
[Drive Node
H5-03
*1
Address]
[Communication
Parity Selection]
*5
1F (Default)
*3 *4
*5
01
*3 *4
*5
02
*3 *4
*5
03
*3 *4
*5
04
Table
Table 2.51 Operation in Gateway Mode
Communication Option Card to Master Drive (Drive
0)
Field bus communication data is written to and read from
the special registers of Drive 0.
H5-06
H5-09
[Drive Transmit
[CE Detection
Wait Time]
Time]
5 ms (factory
*7
≥ 2.0 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
2.51.
C - Master Drive (Drive 0)
D - Slave Drives (Drives 1 to 4)
Master Drive (Drive 0) to Slave Drives (Drives 1 to
• Uses MEMOBUS communications .
• Drive 0 sends data from its special registers to Drives 1
to 4.
2.7 F: Options
b1-01
b1-02
[Frequency
[Run Command
Reference
Selection 1]
Selection 1]
3 [Option PCB]
3 [Option PCB]
2 [Memobus/Modbus
2 [Memobus/Modbus
*8
Communications]
Communications]
2 [Memobus/Modbus
2 [Memobus/Modbus
*8
Communications]
Communications]
2 [Memobus/Modbus
2 [Memobus/Modbus
*8
Communications]
Communications]
2 [Memobus/Modbus
2 [Memobus/Modbus
*8
Communications]
Communications]
4)
337
*8
*8
*8
*8
2