YASKAWA GA800 Programming Manual page 518

Ac drive for industrial applications
Table of Contents

Advertisement

2.11 o: Keypad-Related Settings
You cannot use
to switch between LOCAL and REMOTE Modes.
1 : Enabled
You can use
to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL Mode
is selected,
on the keypad will come on.
WARNING! Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/REMOTE Run Selection = Accept
Existing RUN Command], the drive can start suddenly. Before you change the control source, remove all personnel from the area
around the drive, motor, and load. Sudden starts can cause serious injury or death.
WARNING! Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/RE
Key Function Selection] or b1-07 [LOCAL/REMOTE Run Selection]. Sudden starts can cause serious injury or death. If b1-07 = 1
[Accept Existing RUN Command] and there is an active Run command when you switch from LOCAL to REMOTE Mode, the drive
can start suddenly.
Function Selection
o2-01 = 0 [Disabled]
o2-01 = 1 [Enabled]
o2-02: STOP Key Function Selection
No.
Name
(Hex.)
o2-02
STOP Key Function
Selection
(0506)
0 : Disabled
1 : Enabled
stays enabled when the Run command source has not been assigned to the keypad.
To start the drive again after you push
o2-03: User Parameter Default Value
No.
Name
(Hex.)
o2-03
User Parameter Default
Value
(0507)
When you set o2-03 = 1 [Set defaults], the drive saves changed parameter settings as user parameter setting values in
a part of the memory that is isolated from drive parameters.
When you set A1-03 = 1110 [Initialize Parameters = User Initialization] to initialize the drive, the drive resets the
internal parameter setting values to those user parameter setting values.
0 : No change
1 : Set defaults
Saves changed parameter setting values as user default settings.
Set o2-03 = 1 then push
automatically resets to 0.
518
Table 2.73 Function Settings with o2-01 and b1-07
LOCAL/REMOTE Run Selection
b1-07 = 0 [Disregard Existing RUN
Command]
b1-07 = 1 [Accept Existing RUN
Command]
b1-07 = 0 [Disregard Existing RUN
Command]
b1-07 = 1 [Accept Existing RUN
Command]
V/f
CL-V/f
OLV
CLV
Sets the function to stop the drive with the
source for the drive is REMOTE (external) and not assigned to the keypad.
to stop operation, turn the external Run command OFF and ON again.
V/f
CL-V/f
OLV
CLV
Sets the function to keep the settings of changed parameters as user parameter defaults to use during
initialization.
to save the user parameter setting values. After the drive saves the setting value, o2-03
Switching from LOCAL Mode to
REMOTE Mode
The drive will not switch modes.
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive will
start to run.
When the Run command is active, the drive
will start to run immediately when the mode
switches from LOCAL to REMOTE.
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
button on the keypad when the Run command
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Switching from REMOTE Mode to
LOCAL Mode
The drive will not switch modes.
The drive cannot operate because the Run
command is not enabled.
The drive cannot operate because the Run
command is not enabled.
Default
(Range)
1
(0, 1)
Default
(Range)
0
(0 - 2)

Advertisement

Table of Contents
loading