2.9 L: Protection Functions
L1-03: Motor Thermistor oH Alarm Select
No.
Name
(Hex.)
L1-03
Motor Thermistor oH Alarm
Select
(0482)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows oH3, and operation continues. The output terminal set for Alarm [H2-01 to H2-03 = 10] turns ON.
L1-04: Motor Thermistor oH Fault Select
No.
Name
(Hex.)
L1-04
Motor Thermistor oH Fault
Select
(0483)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
L1-05: Motor Thermistor Filter Time
No.
Name
(Hex.)
L1-05
Motor Thermistor Filter
Time
(0484)
L1-08: oL1 Current Level
No.
Name
(Hex.)
L1-08
oL1 Current Level
(1103)
When L1-08 = 0.0 A, the drive uses E2-01 [Motor Rated Current (FLA)] to detect the motor overload protection. In
PM control mode, the drive uses E5-03 [PM Motor Rated Current (FLA)] to detect the motor overload protection.
When L1-08 ≠ 0.0 A, the set value is the reference for motor overload protection.
440
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when the PTC input signal entered into the drive is at the oH3 [Motor Overheat
Alarm] detection level.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat Fault
(PTC Input)] detection level.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PTC input signal entered to the drive. This parameter
prevents accidental motor overheat faults.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0 A,
you cannot set this value < 10% of drive rated current.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
3
(0 - 3)
Default
(Range)
1
(0 - 2)
Default
(Range)
0.20 s
(0.00 - 10.00 s)
Default
(Range)
0.0 A
(0.0 A or 10% to 150% of
the drive rated current)