1 : Enabled
2 : Automatic Optimization
Note:
Setting 2 is available only when A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM] and in Expert Mode.
b8-02: Energy Saving Gain
No.
Name
(Hex.)
b8-02
Energy Saving Gain
(01CD)
RUN
Expert
Increase the setting value to increase energy saving. If the setting value is too large, the motor will stall.
b8-03: Energy Saving Filter Time
No.
Name
(Hex.)
b8-03
Energy Saving Filter Time
(01CE)
RUN
Expert
Decrease the setting value to increase responsiveness. If the setting value is too low, operation will not be stable.
b8-04: Energy Saving Coefficient Value
No.
Name
(Hex.)
b8-04
Energy Saving Coefficient
Value
(01CF)
Expert
When you use a motor from a different manufacturer, increase the setting value in 5% increments to find the
minimum value for U1-08 [Output Power] at light loads.
When you decrease the setting value, it decreases the output voltage and decreases power consumption. If the setting
value is too low, the motor will stall.
Note:
When you do Rotational Auto-Tuning, the drive will automatically set the energy-saving coefficient.
b8-05: Power Detection Filter Time
No.
Name
(Hex.)
b8-05
Power Detection Filter Time
(01D0)
Expert
Decrease the setting value to increase responsiveness to load changes. If you set the value too low during operation at
light loads, motor speed is not stable.
b8-06: Search Operation Voltage Limit
No.
Name
(Hex.)
b8-06
Search Operation Voltage
Limit
(01D1)
Expert
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The default setting
is for Yaskawa motors.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to measure output power.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the voltage limit for Search Operation as a percentage of the motor rated voltage.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.3 b: Application
Default
(Range)
Determined by A1-02
(0.0 - 10.0)
Default
(Range)
Determined by A1-02,C6-
01 and o2-04
(0.00 - 10.00 s)
Default
(Range)
Determined by C6-01, E2-
11, and o2-04
(0.00 - 655.00)
Default
(Range)
20 ms
(0 - 2000 ms)
Default
(Range)
2
0%
(0 - 100%)