2.11 o: Keypad-Related Settings
Note:
Set this parameter in 10-hour (h) units. When o4-01 = 30, U4-01 [Cumulative Ope Time] = 300 h.
o4-02: Elapsed Operating Time Selection
No.
Name
(Hex.)
o4-02
Elapsed Operating Time
Selection
(050C)
0 : U4-01 Shows Total Power-up Time
Counts the time from when the drive is energized to when it is de-energized.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
o4-03: Fan Operation Time Setting
No.
Name
(Hex.)
o4-03
Fan Operation Time Setting
(050E)
Use monitor U4-03 [Cooling Fan Ope Time] to view the total operation time of the cooling fan. When you replace a
cooling fan, set o4-03 = 0 to reset U4-03. Select o4-03 on the keypad to show the current value of U4-03 in 10-hour
(h) units. If you use the monitor to change o4-03, the recount of U4-03 starts with the o4-03 setting.
Note:
The drive sets o4-03 in 10-hour (h) units. When o4-03 = 30, U4-03 [Cooling Fan Ope Time] will show "300 h".
o4-05: Capacitor Maintenance Setting
No.
Name
(Hex.)
o4-05
Capacitor Maintenance
Setting
(051D)
When you replace a drive, set o4-05 = 0 to reset U4-05. When the o4-05 setting changes, the count of U4-05 starts
again as specified by the setting of o4-05. After you complete the configuration, o4-05 automatically resets to 0.
Note:
The maintenance period changes for different operating environments.
o4-07: Softcharge Relay Maintenance Set
No.
Name
(Hex.)
o4-07
Softcharge Relay
Maintenance Set
(0523)
When you replace a drive, set o4-07 = 0 to reset U4-06. When the o4-07 setting changes, the count of U4-06 starts
again as specified by the setting of o4-07. After you complete the configuration, o4-07 automatically resets to 0.
Note:
The maintenance period changes for different operating environments.
o4-09: IGBT Maintenance Setting
No.
Name
(Hex.)
o4-09
IGBT Maintenance Setting
(0525)
When you replace a drive, set o4-09 = 0 to reset U4-07. When the o4-09 setting changes, the count of U4-07 starts
again as specified by the setting of o4-09. After you complete the configuration, o4-09 automatically resets to 0.
524
V/f
CL-V/f
OLV
CLV
AOLV
Sets the condition that counts the cumulative operation time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the U4-05 [CapacitorMaintenance] monitor value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the U4-06 [PreChargeRelayMainte] monitor value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the U4-07 [IGBT Maintenance] monitor value.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0
(0, 1)
Default
(Range)
0 h
(0 - 9999 h)
Default
(Range)
0%
(0 - 150%)
Default
(Range)
0%
(0 - 150%)
Default
(Range)
0%
(0 - 150%)