YASKAWA GA800 Programming Manual page 470

Ac drive for industrial applications
Table of Contents

Advertisement

2.9 L: Protection Functions
The drive detects overtorque when the output frequency aligns with the frequency reference. Detection does not occur
during acceleration/deceleration. The drive outputs an oL4 [Overtorque Detection 2] and operation stops.
4 : oL @ RUN - Fault
When the Run command is enabled, the drive constantly detects overtorque. The drive outputs an oL4 and operation
stops.
5 : UL @ Speed Agree - Alarm only
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 [Undertorque Detection 2] and operation continues.
6 : UL @ RUN - Alarm only
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL4 and operation
continues.
7 : UL @ Speed Agree - Fault
The drive detects undertorque when the output frequency aligns with the frequency reference. Detection does not
occur during acceleration/deceleration. The drive outputs a UL4 and operation stops.
8 : UL @ RUN - Fault
When the Run command is enabled, the drive constantly detects undertorque. The drive outputs a UL4 and operation
stops
L6-05: Torque Detection Level 2
No.
Name
(Hex.)
L6-05
Torque Detection Level 2
(04A5)
Note:
Overtorque/Undertorque Detection 2 cannot set the detection level for the analog input terminal.
L6-06: Torque Detection Time 2
No.
Name
(Hex.)
L6-06
Torque Detection Time 2
(04A6)
L6-07: Torque Detection Filter Time
No.
Name
(Hex.)
L6-07
Torque Detection Filter Time
(04E5)
L6-08: Mechanical Fatigue Detect Select
No.
Name
(Hex.)
L6-08
Mechanical Fatigue Detect
Select
(0468)
The drive detects mechanical weakening through overtorque or undertorque as specified by the conditions set in L6-
08 to L6-11 [Mechanical Deterioration Detection Settings Parameters]. Set overtorque/undertorque detection
conditions in L6-01 to L6-03 [Torque Detection 1 Settings Parameters]. The drive disables the operation selection set
in L6-01 [Torque Detection Selection 1].
0 : Disabled
The drive does not detect mechanical weakening.
470
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for a primary filter to the torque reference or to the output current used to
detect overtorque/undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed where the drive detects mechanical deterioration and how the drive operates (operation
status) after detection.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
150%
(0 - 300%)
Default
(Range)
0.1 s
(0.0 - 10.0 s)
Default
(Range)
0 ms
(0 - 1000 ms)
Default
(Range)
0
(0 - 8)