4 : HVAC Fan
The drive automatically sets the parameters in
No.
A1-02
b1-04
b1-17
C6-01
C6-02
H2-03
L2-01
L8-03
L8-38
The drive saves the parameters in
Table 2.11 Parameters Saved as User Parameters with the HVAC Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
A2-15
A2-16
5 : Air Compressor
The drive automatically sets the parameters in
Table 2.12 Best Parameter Settings for Air Compressor Applications
No.
A1-02
b1-04
C1-01
C1-02
C6-01
E1-03
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Table 2.10
Table 2.10 Best Parameter Settings for HVAC Applications
Name
Control Method Selection
Reverse Operation Selection
Run Command at Power Up
Normal / Heavy Duty Selection
Carrier Frequency Selection
Terminal M5-M6 Function Selection
Power Loss Ride Through Select
Overheat Pre-Alarm Selection
Carrier Frequency Reduction
Table 2.11
as user parameters.
Parameter No. Saved
C1-01
C1-02
C6-02
E1-03
E1-04
E2-01
H3-11
H3-12
L2-01
Table 2.12
Name
Control Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Normal / Heavy Duty Selection
V/f Pattern Selection
for an HVAC fan application.
b1-01
b1-02
b1-03
b1-04
d2-01
d2-02
o4-12
for an air compressor application.
2.2 A: Initialization Parameters
Optimal Value
0: V/f Control
1: Reverse Disabled
1: Accept Existing RUN Command
1: Normal Duty Rating
3: 8.0 kHz
39: Watt Hour Pulse Output
2: Enabled while CPU Power Active
4: Operate at Reduced Speed (L8-19)
2: Enabled for All Speeds
Name
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Frequency Reference Upper Limit
Frequency Reference Lower Limit
V/f Pattern Selection
Maximum Output Frequency
Motor Rated Current (FLA)
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Power Loss Ride Through Select
kWh Monitor Initialization
Optimal Value
0: V/f Control
1: Reverse Disabled
5.0 s
5.0 s
0: Heavy Duty Rating
F: Custom
2