U2: Fault Trace - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

1.17 U: Monitors
No.
Name
(Hex.)
U1-19
MEMOBUS/Modbus Error
Code
(0066)
U1-21
AI-A3 Term V1 Level
(0077)
U1-22
AI-A3 Term V2 Level
(072A)
U1-23
AI-A3 Term V3 Level
(072B)
U1-24
Input Pulse Monitor
(007D)
U1-25
SoftwareNumber Flash
(004D)
U1-26
SoftwareNumber ROM
(005B)
U1-50
Virtual Analog Input
(1199)
Expert
U1-91
Output Voltage
(154E)
Expert

U2: Fault Trace

No.
Name
(Hex.)
U2-01
Current Fault
(0080)
U2-02
Previous Fault
(0081)
U2-03
Freq Reference@Fault
(0082)
U2-04
Output Freq @ Fault
(0083)
114
V/f
CL-V/f
OLV
CLV
AOLV
Shows the contents of the MEMOBUS/Modbus communication error where 1 = (error) and 0 = (no
error).
For example, U1-19 shows "00000001" when a CRC error occurs.
bit 0 : CRC Error
bit 1 : Data Length Error
bit 2 : Not used (normal value of 0).
bit 3 : Parity Error
bit 4 : Overrun Error
bit 5 : Framing Error
bit 6 : Timed Out
bit 7 : Not used (normal value of 0).
V/f
CL-V/f
OLV
CLV
AOLV
Shows the analog reference of terminal V1 on analog input option card AI-A3.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the analog reference of terminal V2 on analog input option card AI-A3.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the analog reference of terminal V3 on analog input option card AI-A3.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the frequency to pulse train input terminal RP.
Unit: 1 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the FLASH ID.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the ROM ID.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the virtual analog input value.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the drive internal output voltage reference.
Unit: 0.1 V
V/f
CL-V/f
OLV
CLV
AOLV
Shows the fault that the drive has when viewing the monitor.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the fault that occurred most recently.
V/f
CL-V/f
OLV
CLV
AOLV
Shows the frequency reference at the fault that occurred most recently.
Use U1-01 [Frequency Reference] to monitor the actual frequency reference value.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the output frequency at the fault that occurred most recently.
Use U1-02 [Output Frequency] to monitor the actual output frequency.
Unit: 0.01 Hz
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
MFAO Signal Level
No signal output available
10 V = 100% (-10 V to +10
V)
10 V = 100% (-10 V to +10
V)
10 V = 100% (-10 V to +10
V)
Determined by H6-02
No signal output available
No signal output available
Determined by H7-40
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available

Advertisement

Table of Contents
loading

Table of Contents