H6: Pulse Train Input/Output - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

2.8 H: Terminal Functions
Note:
• The setting value automatically returns to H5-20 = 0 after you enable MEMOBUS/Modbus communications parameter changes.
• The setting values of these parameters are enabled:
–H5-01 [Drive Node Address]
–H5-02 [Communication Speed Selection]
–H5-03 [Communication Parity Selection]
–H5-06 [Drive Transmit Wait Time]
H5-22: Speed Search from MODBUS
No.
Name
(Hex.)
H5-22
Speed Search from
MODBUS
(11CF)
0 : Disabled
1 : Enabled
If you set H5-22 = 1 and H1-xx = 62 [Speed Search from Fref] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
H5-25: Function 5A Register 1 Selection
No.
Name
(Hex.)
H5-25
Function 5A Register 1
Selection
(1589)
RUN
H5-26: Function 5A Register 2 Selection
No.
Name
(Hex.)
H5-26
Function 5A Register 2
Selection
(158A)
RUN
H5-27: Function 5A Register 3 Selection
No.
Name
(Hex.)
H5-27
Function 5A Register 3
Selection
(158B)
RUN
H5-28: Function 5A Register 4 Selection
No.
Name
(Hex.)
H5-28
Function 5A Register 4
Selection
(158C)
RUN

H6: Pulse Train Input/Output

H6 parameters set the drive pulse train input and pulse train monitor. These parameters select input and monitor
parameters and adjust the pulse train frequency.
A pulse train signal with a maximum single pulse of 32 kHz can be input to the drive input terminal RP. You can use
the pulse train signal as the frequency reference, PID feedback value, PID setpoint value, and speed feedback for V/f
Control mode.
426
V/f
CL-V/f
OLV
CLV
AOLV
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH).
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0
(0, 1)
Default
(Range)
0044H (U1-05)
(0000H - FFFFH)
Default
(Range)
0045H (U1-06)
(0000H - FFFFH)
Default
(Range)
0042H (U1-03)
(0000H - FFFFH)
Default
(Range)
0049H (U1-10)
(0000H - FFFFH)