2.8 H: Terminal Functions
H2-06: Watt Hour Output Unit Selection
No.
Name
(Hex.)
H2-06
Watt Hour Output Unit
Selection
(0437)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh unit
for each pulse output.
Note:
• When the power value is a negative value (regenerative state), the drive does not count Watt hours.
• When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive to
lose control power, the Watt hour count will reset.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
H2-07: Modbus Register 1 Address Select
No.
Name
(Hex.)
H2-07
Modbus Register 1 Address
Select
(0B3A)
Sets the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the bit
in H2-08 [Modbus Register 1 Bit Select].
H2-08: Modbus Register 1 Bit Select
No.
Name
(Hex.)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the address
in H2-07 [Modbus Register 1 Address Select].
H2-09: Modbus Register 2 Address Select
No.
Name
(Hex.)
H2-09
Modbus Register 2 Address
Select
(0B3C)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and
uses the bit in H2-10 [Modbus Register 2 Bit Select].
384
V/f
CL-V/f
OLV
CLV
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
Figure 2.88 Example MFDO when Configured for Watt Hours
V/f
CL-V/f
OLV
CLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0
(0 - 4)
Default
(Range)
0001
(0001 - 1FFF)
Default
(Range)
0000
(0000 - FFFF)
Default
(Range)
0001
(0001 - 1FFF)