Setting Value
Function
60
DC Injection Braking
Command
61
Speed Search from Fmax
62
Speed Search from Fref
63
Field Weakening
65
KEB Ride-Thru 1
Activate (N.C.)
66
KEB Ride-Thru 1
Activate (N.O.)
67
Communications Test
Mode
68
High Slip Braking
6A
Drive Enable
71
Torque Control
72
Zero Servo
75
Up 2 Command
76
Down 2 Command
77
ASR Gain (C5-03) Select
78
Analog TorqueRef
Polarity Invert
7A
KEB Ride-Thru 2
Activate (N.C.)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to start speed search using an external reference although b3-01 = 0 [Speed Search Selection at Start
= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start
= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01
[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
CL-V/f
OLV
CLV
AOLV
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use high-slip braking to stop the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to switch between torque control and speed control.
ON : Torque Control
OFF : Speed Control
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to hold a stopped motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is activated.
Set this function and H1-xx = 76 [Down 2 Command] together.
Note:
When you use this function, use d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit] to set the optimal
bias limit value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to decrease the frequency reference bias value to decelerate the motor when the terminal is activated.
Set this function and H1-xx = 75 [Up 2 Command] at the same time.
Note:
When you use this function, use d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit] to set the optimal
bias limit value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASR
Proportional Gain 2].
ON : C5-03
OFF : C5-01
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rotation direction of the external torque reference.
ON : External torque reference reverse direction
OFF : External torque reference forward direction
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.10 H: Terminal Functions
Ref.
374
375
375
375
375
376
376
376
376
376
377
377
378
379
379
379
1
65