2.8 H: Terminal Functions
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on
the input side turns off after the time set with b8-51 [Standby Mode Wait Time] elapses.
66: Comparator1
Setting Value
Function
66
Comparator1
A - H2-24
[Comparator 1 On-Delay Time]
Note:
The drive compares the monitors set with H2-20 as absolute values.
67: Comparator2
Setting Value
Function
67
Comparator2
404
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values of H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator 1 On-Delay Time].
Figure 2.101 Comparator 1 Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the values of H2-
27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30 [Comparator 2 On-Delay Time].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
B - H2-25
[Comparator 1 Off-Delay Time]
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming