YASKAWA GA800 Programming Manual page 315

Ac drive for industrial applications
Table of Contents

Advertisement

E9-07: Motor Rated Power
No.
Name
(Hex.)
E9-07
Motor Rated Power
(11EA)
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Power (kW)].
E9-08: Motor Pole Count
No.
Name
(Hex.)
E9-08
Motor Pole Count
(11EB)
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
E9-09: Motor Rated Slip
No.
Name
(Hex.)
E9-09
Motor Rated Slip
(11EC)
The setting value of this parameter is the slip compensation reference value.
The drive uses the setting values of E9-03, E9-04, and E9-08 to calculate this parameter. When Motor Rated Slip = 0,
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Slip].
Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
E9-10: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E9-10
Motor Line-to-Line
Resistance
(11ED)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the single-phase resistance.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test report
from the motor manufacturer. You can calculate the motor line-to-line resistance with one of these formulas:
• E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated power in the units from o1-58 [Motor Power Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated slip.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the line-to-line resistance for the motor stator windings.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
2.6 E: Motor Parameters
Default
(Range)
Determined by E9-02 and
o2-04
(0.00 - 650.00 HP)
Default
(Range)
4
(2 to 120)
Default
(Range)
0.000 Hz
(0.000 - 20.000 Hz)
Default
(Range)
Determined by o2-04
(0.000 - 65.000 Ω)
315
2

Advertisement

Table of Contents
loading