E4: Motor 2 Parameters - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

2.6 E: Motor Parameters
E3-12: Motor 2 Mid Point B Voltage
No.
Name
(Hex.)
E3-12
Motor 2 Mid Point B Voltage
(0346)
Expert
Note:
• Set this parameter to 0.0 to disable the function.
• When you initialize the drive, this parameter is reset to the default value.
• The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).
E3-13: Motor 2 Base Voltage
No.
Name
(Hex.)
E3-13
Motor 2 Base Voltage
(0347)
Expert
Note:
• When you initialize the drive, this parameter is reset to the default value.
• The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).

E4: Motor 2 Parameters

E4 parameters [Motor 2 Parameters] set induction motor data. To switch drive operation from one motor to a
different motor, configure motor 2.
Auto-Tuning automatically sets the E4 parameters to the best values for the application. If you cannot do Auto-
Tuning, set the E4 parameters manually.
Note:
E3-xx and E4-xx are available when H1-xx = 16 [MFDI Function Select = Motor 2 Selection].
E4-01: Motor 2 Rated Current
No.
Name
(Hex.)
E4-01
Motor 2 Rated Current
(0321)
Note:
• If E4-01 ≤ E4-03 [Motor 2 Rated No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error] will be detected.
• The default settings and setting ranges are in these units:
–0.01 A: 2004 to 2042, 4002 to 4023
–0.1 A: 2056 to 2415, 4031 to 4720
The value set for E4-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current written on the motor nameplate. Auto-Tuning automatically sets the value of E4-01 to the
value input for [Motor Rated Current].
E4-02: Motor 2 Rated Slip
No.
Name
(Hex.)
E4-02
Motor 2 Rated Slip
(0322)
The value set in E4-02 becomes the base slip compensation value. The drive sets this parameter during Rotational
Auto-Tuning and Stationary Auto-Tuning. If you cannot do Auto-Tuning, use the information written on the motor
nameplate and this formula to calculate the motor rated slip:
308
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern
for the constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f pattern for the
constant output range. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated current for motor 2 in amps.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated slip for motor 2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
Default
(Range)
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Default
(Range)
Determined by o2-04, C6-01
(0.000 - 20.000 Hz)