2.3 b: Application
b3-26: Direction Determination Level
No.
Name
(Hex.)
b3-26
Direction Determination
Level
(01C7)
Expert
b3-27: Speed Search RUN/BB Priority
No.
Name
(Hex.)
b3-27
Speed Search RUN/BB
Priority
(01C9)
Expert
Executes Speed Search from Fmax or Fref [H1-xx = 61/62] for initial speed searches or from the MFDI terminal.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
b3-29: Speed Search Back-EMF Threshold
No.
Name
(Hex.)
b3-29
Speed Search Back-EMF
Threshold
(077C)
Expert
To make adjustments, gradually decrease the setting value. If you decrease the setting value too much, speed search
will not operate correctly.
b3-31: Spd Search Current Reference Lvl
No.
Name
(Hex.)
b3-31
Spd Search Current
Reference Lvl
(0BC0)
Expert
Set this parameter as a ratio of E2-03 [Motor No-Load Current]. The setting is a ratio with respect to 30% of the
motor rated current when E2-03 ≤ E2-01 [Motor Rated Current] × 0.3.
Note:
The setting is a ratio with respect to E9-06 [Motor Rated Current (FLA)] × 0.5 when A1-02 = 8 [Control Method Selection = EZOLV].
b3-32: Spd Search Current Complete Lvl
No.
Name
(Hex.)
b3-32
Spd Search Current
Complete Lvl
(0BC1)
Expert
The Current Detection Speed Search gradually decreases the output frequency to search for the motor speed when the
output current is equal to or less than Speed Search Current Complete Level.
Set this parameter as a ratio of E2-03 [Motor No-Load Current]. The setting is a ratio with respect to 30% of the
motor rated current when E2-03 ≤ E2-01 [Motor Rated Current] × 0.3.
Note:
The setting is a ratio with respect to E9-06 [Motor Rated Current (FLA)] × 0.5 when A1-02 = 8 [Control Method Selection = EZOLV].
218
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to find the motor rotation direction. Increase the value if the drive cannot find the
direction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the conditions necessary to start Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the induced voltage for motors that use Speed Search. The drive will start Speed Search when
the motor induced voltage level is the same as the setting value. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that decreases the output current during Current Detection Speed Search.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current level that completes Speed Search.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Default
(Range)
1000
(40 to 60000)
Default
(Range)
0
(0, 1)
Default
(Range)
10%
(0 - 10%)
Default
(Range)
1.50
(1.50 - 3.50)
Default
(Range)
1.20
(0.00 - 1.49)

Advertisement

Table of Contents
loading

Table of Contents