Setting Value
Function
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset Procedure
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time
Selection 2
1B
Programming Lockout
1E
Reference Sample Hold
20 to 2F
External fault
30
PID Integrator Reset
31
PID Integrator Hold
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10
[Up Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to operate the motor in reverse at the Jog Frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
trying to reset a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Operate motor 2
OFF : Operate motor 1
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
ON : PID control disabled
OFF : PID control enabled
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 7[Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/
Deceleration Time 3 [C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold the frequency reference at
that frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (NO-Always-Ramp)
21 : External Fault (NC-Always-Ramp)
22 : External Fault (NO-@Run-Ramp)
23 : External Fault (NC-@Run-Ramp)
24 : External Fault (NO-Always-Coast)
25 : External Fault (NC-Always-Coast)
26 : External Fault (NO-@Run-Coast)
27 : External Fault (NC-@Run-Coast)
28 : External Fault (NO-Always-FStop)
29 : External Fault (NC-Always-FStop)
2A : External Fault (NO-@Run-FStop)
2B : External Fault (NC-@Run-FStop)
2C : External Fault (NO-Always-Alarm)
2D : External Fault (NC-Always-Alarm)
2E : External Fault (NO-@Run-Alarm)
2F : External Fault (NC-@Run-Alarm)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to hold the integral value of the PID control while the terminal is activated.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.10 H: Terminal Functions
Ref.
366
367
367
368
368
368
369
369
370
370
370
370
371
371
372
1