F) Setting Of Acceleration/Deceleration Time And Acceleration/Deceleration Pattern - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

5.5
(F) Setting of acceleration/deceleration time and
acceleration/deceleration pattern
Purpose
To set the motor acceleration/
deceleration time
To set the acceleration/
deceleration pattern suitable for
an application
To command smooth speed
transition with terminals
Starting frequency
5.5.1
Setting the acceleration and deceleration time
The following parameters are used to set motor acceleration/deceleration time.
Set a larger value for a slower acceleration/deceleration, or a smaller value for a faster acceleration/deceleration.
For the acceleration time at automatic restart after instantaneous power failure, refer to Pr.611 Acceleration time at a restart
(on
page 446
and
page
Pr.
Name
Acceleration/
20
deceleration
F000
reference
frequency
Acceleration/
21
deceleration time
F001
increments
16
Jog acceleration/
F002
deceleration time
611
Acceleration time
F003
at a restart
7
Acceleration time
F010
8
Deceleration time
F011
Second
44
acceleration/
F020
deceleration time
45
Second
F021
deceleration time
Acceleration/
147
deceleration time
F022
switching
frequency
Acceleration time
791
in low-speed
F070
range
216
5. PARAMETERS

5.5 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern

Acceleration/deceleration time
Acceleration/deceleration pattern
and backlash measures
Remote setting function
Starting frequency and start-time
hold
451).
Initial value
Setting range
FM
CA
60 Hz
50 Hz 1 to 590 Hz
0
0
1
0.5 s
0 to 3600 s
0 to 3600 s
9999
9999
*1
5 s
0 to 3600 s
*2
15 s
*1
10 s
0 to 3600 s
*1
30 s
5 s
0 to 3600 s
0 to 3600 s
9999
9999
0 to 590 Hz
9999
9999
0 to 3600 s
9999
9999
Parameter to set
Pr.7, Pr.8,
P.F000 to P.F003,
Pr.16, Pr.20,
P.F010, P.F011,
Pr.21, Pr.44,
P.F020 to P.F022,
Pr.45, Pr.147,
P.F070, P.F071
Pr.611, Pr.791,
Pr.792
P.F100, P.F200
Pr.29, Pr.140
to P.F203
to Pr.143
P.F101
Pr.59
P.F102, P.F103
Pr.13, Pr.571
Description
Set the frequency that is the basis of acceleration/deceleration time.
As acceleration/deceleration time, set the time required to change
the frequency from a stop status (0 Hz) to the frequency set in Pr.20
and vice versa.
Increment: 0.1 s
Select the increment for the acceleration/
deceleration time setting.
Increment: 0.01 s
Set the acceleration/deceleration time (time required to change the
frequency from a stop status (0 Hz) to the frequency set in Pr.20 and
vice versa) for JOG operation. (Refer to
Set the acceleration time for restart (from stop status to Pr.20).
Standard acceleration time (for example, Pr.7) is applied as the
acceleration time at restart. (Refer to
Set the motor acceleration time (time required to change the
frequency from a stop status (0 Hz) to the frequency set in Pr.20).
Set the motor deceleration time (time required to change the
frequency from the frequency set in Pr.20 to stop status (0 Hz)).
Set the acceleration/deceleration time used while the RT signal is
ON.
Set the deceleration time used while the RT signal is ON.
The acceleration time applies to the deceleration time.
Set the frequency where the acceleration/deceleration time switches
to the time set in Pr.44 and/or Pr.45.
Function disabled.
Set the acceleration time in a low-speed range (less than 1/10 of the
rated motor frequency).
The acceleration time set in Pr.7 is applied. (While the RT signal is
ON, the second function is enabled.)
Refer to page
216
219
222
225,
226
page
248.)
page 446
and
page
451.)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents