5.8.2
Monitor item selection on operation panel or via
communication
The monitor item to be displayed on the operation panel or the parameter unit can be selected.
Pr.
Name
52
Operation panel main
M100
monitor selection
774
Operation panel monitor
M101
selection 1
775
Operation panel monitor
M102
selection 2
776
Operation panel monitor
M103
selection 3
992
Operation panel setting dial
M104
push monitor selection
170
Watt-hour meter clear
M020
563
Energization time carrying-
M021
over times
268
Monitor decimal digits
M022
selection
891
Cumulative power monitor
M023
digit shifted times
171
Operation hour meter clear 9999
M030
564
Operating time carrying-
M031
over times
290
Monitor negative output
M044
selection
1018
Monitor with sign selection 9999
M045
1106
Torque monitor filter
M050
1107
Running speed monitor
M051
filter
1108
Excitation current monitor
M052
filter
288
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
selectionpage 288
Initial value
Setting range
0, 5 to 14, 17, 18,
20, 23 to 25, 34, 38,
0 (output
40 to 45, 50 to 57,
frequency)
61, 62, 64, 67 to 69,
81 to 96, 98, 100
1 to 3, 5 to 14, 17,
18, 20, 23 to 25, 34,
38, 40 to 45, 50 to
9999
57, 61, 62, 64, 67 to
69, 81 to 96, 98,
100, 9999
0 to 3, 5 to 14, 17,
18, 20, 23 to 25, 34,
0 (set
38, 40 to 45, 50 to
frequency)
57, 61, 62, 64, 67 to
69, 81 to 96, 98,
100
0
10
9999
9999
(0 to 65535)
0
(Read-only)
0
9999
1
9999
0 to 4
9999
9999
0
9999
(0 to 65535)
0
(Read-only)
0
0 to 7
0
9999
0 to 5 s
9999
9999
0 to 5 s
9999
9999
0 to 5 s
9999
9999
Description
Select the item monitored on the operation panel or
parameter unit.
Refer to
page 289
for the monitor item selection.
Each of the initial items monitored on the operation panel or
parameter unit in the monitor mode (output frequency,
output current, and output voltage) can be switched to a
user-designated item.
9999: Follows the Pr.52 setting.
Select the monitor item displayed on the operation panel at
the time when the setting dial is pressed.
Set "0" to clear the watt-hour meter.
Set "10" to monitor the cumulative power in the range of 0 to
9999 kWh via communication.
Set "9999" to monitor the cumulative power in the range of 0
to 65535 kWh via communication.
The number of times that the cumulative energization time
exceeded 65535 hours is displayed (read-only).
Value is displayed in 1 increments (an integer).
Value is displayed in 0.1 increments.
No function
Set the number of digits to move the decimal point of the
cumulative energy monitored value to the left.
The readout peaks out at the upper limit of readout.
The function of moving the decimal point is not available.
The readout is reset to 0 when it exceeds the upper limit.
Set "0" to clear the operation hour meter.
The readout is always 9999. Nothing changes when "9999"
is set.
The number of times that the operating time reaches 65535
hours is displayed. Read-only.
Set the availability of negative signals output via terminal
AM, to the operation panel, and through communication.
Select the item group to enable the indication of negative
signed numbers.
The filter time constant is selectable for monitoring of the
torque. A larger setting results in slower response.
0.3 s filter
The filter time constant is selectable for monitoring of the
running speed. A larger setting results in slower response.
0.08 s filter
The filter time constant is selectable for monitoring of the
motor excitation current. A larger setting results in slower
response.
0.3 s filter