Mitsubishi Electric FR-F820-00046 Instruction Manual page 471

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

00023 00038 00105 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800 02160 02600 03250 03610 04320 04810 05470 06100 06830
Model FR-F840-[]
0.75K 1.5K 2.2K 3.7K 5.5K 7.5K
Trigger level
1.5
2.5
reference current (A)
07700 08660 09620 10940 12120
Model FR-F842-[]
355K 400K 450K 500K 560K
Trigger level
610
683
reference current (A)
 Digital source (monitor item) selection
• Select the digital sources (input/output signals) to be set to Pr.1038 to Pr.1045 from the following table. When a value
other than the ones in the following table is set, "0" (OFF) is applied for indication.
Setting
Signal name
value
0
1
STF
2
STR
3
AU
4
RT
5
RL
6
RM
7
RH
8
JOG
9
MRS
10
STP (STOP)
11
RES
12
CS
21
X0
22
X1
23
X2
24
X3
25
X4
26
X5
27
X6
28
X7
29
X8
30
X9
31
X10
32
X11
33
X12
34
X13
35
X14
36
X15
37
DY
 Trigger setting (Pr.1025, Pr.1035 to Pr.1037, Pr.1046, Pr.1047)
• Set the trigger generating conditions and the trigger target channels.
Pr.1025
setting
0
Trace starts when inverter enters an fault status (protective function activated)
1
Trace starts when analog monitor satisfies trigger conditions
2
Trace starts when digital monitor satisfies trigger conditions
3
Trace starts when either of analog or digital monitor satisfies trigger conditions
4
Trace starts when both of analog or digital monitor satisfies trigger conditions (AND)
• Set the trigger generation conditions for the analog monitor.
Pr.1036
setting
Sampling starts when the analog data targeted for the trigger exceeds the value specified
0
at the trigger level
Sampling starts when the analog data targeted for the trigger falls below the value specified
1
at the trigger level
470
5. PARAMETERS
5.11 (A) Application parameters
11K
15K 18.5K 22K
4
6
9
12
17
23
770
866
962
Remarks
For the details of the signals, refer to
page
355.
For the details of the signals, refer to
the Instruction Manual of the FR-
A8AX (option).
Trigger generating conditions
Trigger generation conditions
30K
37K
45K
55K
75K
31
38
44
57
71
86
Setting
Signal name
value
101
RUN
102
SU
103
IPF
104
OL
105
FU
106
ABC1
107
ABC2
121
DO0
122
DO1
123
DO2
124
DO3
125
DO4
126
DO5
127
DO6
128
RA1
129
RA2
130
RA3
90K 110K 132K 160K 185K 220K 250K 280K 315K
110
144
180
216
260
325
Remarks
For the details of the signals, refer to
page
312.
For the details of the signals, refer to
the Instruction Manual of the FR-
A8AY (option).
For the details of the signals, refer to
the Instruction Manual of the FR-
A8AR (option).
Selection of trigger
target channel
Pr.1035
Pr.1046
Pr.1035, Pr.1046
Pr.1035, Pr.1046
Trigger level setting
Set the trigger level from 600 to
1400 (-400 to 400%
Pr.1037.
361
432
481
547
*1
) in