 Output signal
Terminal
Type
Terminal name
symbol
A1, B1,
Relay output 1 (fault
*1
output)
C1
A2, B2,
Relay output 2
*1
C2
*1
Inverter running
RUN
*1
Up to frequency
SU
*1
Overload warning
OL
Instantaneous
*1
IPF
power failure
Frequency
*1
FU
detection
Open collector
SE
output common
For meter
*2
FM
NPN open collector
output
Analog voltage
AM
output
Analog current
*3
CA
output
*1
The terminal function can be selected by Pr.190 to Pr.196 (Output terminal function selection). (Refer to
*2
Terminal FM is provided in the FM-type inverter.
*3
Terminal CA is provided in the CA-type inverter.
60
2. INSTALLATION AND WIRING
2.6 Control circuit
Terminal function description
1 changeover contact output that indicates that an inverter's
protective function has been activated and the outputs are
stopped.
Fault: discontinuity across B and C (continuity across A and
C), Normal: continuity across B and C (discontinuity across
A and C)
1 changeover contact output
The output is in LOW state when the inverter output
frequency is equal to or higher than the starting frequency
(initial value: 0.5 Hz). The output is in HIGH state during stop
or DC injection brake operation.
The output is in LOW state when the
output frequency is within the set
frequency range ±10% (initial value). The
output is in HIGH state during
acceleration/deceleration and at a stop.
The output is in LOW state when stall
prevention is activated by the stall
prevention function. The output is in HIGH
state when stall prevention is canceled.
The output is in LOW state when an
instantaneous power failure occurs or
when the undervoltage protection is
activated.
The output is in LOW state when the
inverter output frequency is equal to or
higher than the preset detection
frequency, and is in HIGH state when it is
less than the preset detection frequency.
Common terminal for terminals RUN, SU, OL, IPF, FU
Among several monitor items such as
output frequency, select one to output it
via these terminals. The signal is not
output during an inverter reset.
The size of output signal is proportional to
the magnitude of the corresponding
monitor item.
Use Pr.55, Pr.56, and Pr.866 to set full
scales for the monitoring output
frequency, output current, and torque.
(Refer to
page
297.)
Rated specification
Contact capacity: 230
VAC 0.3 A (power factor =
0.4), 30 VDC 0.3 A
Permissible load: 24 VDC
(27 VDC at maximum) 0.1
A
(The voltage drop is 2.8 V
at maximum while the
signal is ON.)
The open collector
Fault code (4
transistor is ON
bits) output.
(conductive) in LOW
(Refer to
page
state.
327.)
The transistor is OFF (not
conductive) in HIGH
state.
Output item:
Permissible load current:
output
2 mA, pulse for full scale:
frequency (initial
1440 pulses/s
setting)
This terminal
can be used for
open collector
Maximum output pulse:
outputs
50k pulses/s, permissible
depending on
load current: 80 mA
the Pr.291
setting.
Output signal: 0 to ±10
VDC, permissible load
current: 1 mA (load
Output item:
impedance 10 kΩ or
output
more), resolution: 8 bits
frequency (initial
setting)
Load impedance: 200 to
450 Ω, output signal: 0 to
20 mADC
page
312.)
Refer
to page
312
312
312
319
273
446,
451
319
297
245
297
297