Mitsubishi Electric FR-F820-00046 Instruction Manual page 319

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

NOTE
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output when the set
time of (Pr.157 + Pr.289) elapses.
• The signal output for the PLC function (see
Pr.289 setting (not filtered for responsivity).
 Inverter operation ready signal (RY signal) and Inverter running signals
(RUN and RUN3 signals)
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches the setting of Pr.13 Starting frequency or higher, the Inverter running (RUN)
signal turns ON. The signals are OFF while the inverter is stopped or during the DC injection brake operation.
• The Inverter running and start command ON (RUN3) signal is ON while the inverter is running or while the start command
signal is ON (When the start command signal is ON, the RUN3 signal is ON even while the inverter's protective function
is activated or while the MRS signal is ON.) The RUN3 signal is ON even during the DC injection brake operation, and the
signal is OFF when the inverter stops.
Power
ON
supply
STF
RH
Pr. 13
Reset
processing
RY
RUN
RUN3
• The ON/OFF state of each signal according to the inverter operating status is shown in the matrix below.
Start signal
Output
OFF
signal
(inverter
stopped)
*3
ON
RY
RUN
OFF
RUN3
OFF
*1
The signal is OFF during power failure or undervoltage.
*2
This means the state during a fault occurrence or while the MRS signal is ON, etc.
*3
The signal is OFF while power is not supplied to the main circuit.
• To use the RY, RUN, or RUN3 signal, set the corresponding number selected from the following table in any of Pr.190 to
Pr.196 (Output terminal function selection) to assign the function to an output terminal.
Output signal
RY
RUN
RUN3
318
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
ON
OFF
ON
DC injection brake
operation point
DC injection
brake
operation
ON
ON
OFF
ON
OFF
Start signal
Start signal
ON
ON
(inverter
(inverter
stopped)
running)
ON
ON
OFF
ON
ON
ON
Pr.190 to Pr.196 settings
Positive logic
Negative logic
11
111
0
100
45
145
page
462) and for the fault code output (see
OFF
Time
OFF
DC
Inverter output shutoff
injection
brake
Start signal
Start signal
operation
ON
ON
OFF
OFF
OFF
ON
ON
OFF
page
325) are not affected by the
Automatic restart after instantaneous
*2
power failure
During coasting
Start signal
Start signal
OFF
ON
OFF
*1
ON
OFF
ON
OFF
Inverter
running
after
restart
ON
ON
ON