• In order to decelerate the motor to a stop, turn OFF the STP (STOP) signal once.
Forward
Stop
rotation start
Reverse
rotation start
ON
STF
STR
STP (STOP) ON
3-wire type connection example (Pr.250 = "9999")
NOTE
• The STP (STOP) signal is assigned to terminal STP (STOP) in the initial status. Set "25" in any of Pr.178 to Pr.189 to assign
the STP (STOP) signal to another terminal.
• When the JOG operation is enabled by turning ON the JOG signal, the STOP signal will be disabled.
• Even when the output is stopped by turning ON the MRS signal, the self-holding function is not canceled.
 Start signal selection
STF
OFF
OFF
ON
ON
Parameters referred to
Pr.4 to Pr.6 (multi-speed
setting)page 249
Pr.178 to Pr.189 (Input terminal function
STF
Inverter
STR
STP (STOP)
SD
Time
ON
OFF
OFF
STR
OFF
ON
OFF
ON
selection)page 355
Stop
Start
Forward rotation
/reverse rotation
ON
STF
ON
STR
STP (STOP) ON
OFF
3-wire type connection example (Pr.250 = "8888")
Pr.250 setting and inverter condition
0 to 100 s, 9999
Stop
Reverse rotation
Forward rotation
Stop
5.9 (T) Multi-function input terminal parameters
STF
Inverter
STP (STOP)
STR
SD
Time
ON
OFF
1000 to 1100 s, 8888
Stop
Forward rotation
Reverse rotation
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
361