Mitsubishi Electric FR-F820-00046 Instruction Manual page 521

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

Pr.
C18 (920)
41920
42110
C19 (920)
43920
C8 (930)
41930
C9 (930)
42120
C10 (931)
41931
C11 (931)
42121
C38 (932)
41932
42122
C39 (932)
43932
C40 (933)
41933
42123
C41 (933)
43933
C42 (934)
41934
42124
C43 (934)
43934
C44 (935)
41935
42125
C45 (935)
43935
1000 to 1999
45000 to 45999
• Fault history
Register
40501
Fault record 1
40502
Fault record 2
40503
Fault record 3
40504
Fault record 4
40505
Fault record 5
40506
Fault record 6
40507
Fault record 7
40508
Fault record 8
• Product profile
Register
44001
44002
44003
44004
44005
44006
44007
44008
44009
44010
44011
44012
44013
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
520
5. PARAMETERS
5.12 (N) Communication operation parameters
Register
Name
Terminal 1 gain command (torque) Read/write
Terminal 1 gain (torque)
Terminal 1 gain (torque)
(terminal analog value)
Current output bias signal
Current output bias current
Current output gain signal
Current output gain current
Terminal 4 bias command (torque) Read/write
Terminal 4 bias (torque)
Terminal 4 bias (torque)
(terminal analog value)
Terminal 4 gain command (torque) Read/write
Terminal 4 gain (torque)
Terminal 4 gain (torque)
(terminal analog value)
PID display bias coefficient
PID display bias analog value
PID display bias analog value
(terminal analog value)
PID display gain coefficient
PID display gain analog value
PID display gain analog value
(terminal analog value)
For details on parameter names,
refer to the parameter list
132).
Definition
Read/write
Read
Read
Read
Read
Read
Read
Read
Definition
Model (1st and 2nd characters)
Model (3rd and 4th characters)
Model (5th and 6th characters)
Model (7th and 8th characters)
Model (9th and 10th characters)
Model (11th and 12th characters)
Model (13th and 14th characters)
Model (15th and 16th characters)
Model (17th and 18th characters)
Model (19th and 20th characters)
Capacity (1st and 2nd characters)
Capacity (3rd and 4th characters)
Capacity (5th and 6th characters)
Read/write
Read/write
Read
Read/write
Read/write
Read/write
Read/write
Read/write
Read
Read/write
Read
Read/write
Read/write
Read
Read/write
Read/write
Read
(page
Read/write
Read/write
Being 2 bytes in length, the data is stored as H00○○.
Refer to the lowest 1 byte for the error code. (For details on
error codes, refer to
The fault history is cleared by writing to register 40501.
Set any value as data.
Read/write
Read
Read
Read
Read
The model name can be read in ASCII code.
Read
"H20" (blank code) is set for blank area.
Example) FR-F840-1 (FM type):
Read
H46, H52, H2D, H46, H38, H34, H30, H2D, H31, H20 ... H20
Read
Read
Read
Read
Read
The inverter rated capacity can be read in ASCII code.
Data read is displayed in increments of 0.1 kW (rounded
Read
down to one decimal place).
"H20" (blank code) is set for blank area.
Read
Example) 0.75K: " 7" (H20, H20, H20, H20, H20, H37)
Remarks
Analog value (%) set in C19 (920)
Analog value (%) of voltage applied to
terminal 1
Analog value (%) set in C9 (930)
Analog value (%) set in C11 (931)
Analog value (%) set in C39 (932)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C41 (933)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C43 (934)
Analog value (%) of the current (voltage)
applied to terminal 4
Analog value (%) set in C45 (935)
Analog value (%) of the current (voltage)
applied to terminal 4
The parameter number + 44000 is the
register number.
Remarks
page
566.)