NOTE
• To prevent an electric shock, always earth (ground) the motor and inverter.
• Do not install a power factor correction capacitor, surge suppressor, or capacitor type filter on the inverter's output side. Doing
so will cause the inverter shut off or damage the capacitor or surge suppressor. If any of the above devices is connected,
immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact the
manufacturer of the molded case circuit breaker.
• Electromagnetic wave interference:
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. To minimize interference, enabling the built-in EMC filter
or installing an external EMC filters is effective. (Refer to
• For details of options and peripheral devices, refer to the respective Instruction Manual.
• A PM motor cannot be driven by the commercial power supply.
• A PM motor is a motor with permanent magnets embedded inside. High voltage is generated at the motor terminals while the
motor is running. Before closing the contactor at the output side, make sure that the inverter power is ON and the motor is
stopped.
2.1.2

Peripheral devices

Check the model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the following table for right selection.
 LD rating (Pr.570 Multiple rating setting = "1")
• 200 V class
Motor
output
Inverter model
(kW)
0.75
FR-F820-00046(0.75K)
1.5
FR-F820-00077(1.5K)
2.2
FR-F820-00105(2.2K)
3.7
FR-F820-00167(3.7K)
5.5
FR-F820-00250(5.5K)
7.5
FR-F820-00340(7.5K)
11
FR-F820-00490(11K)
15
FR-F820-00630(15K)
18.5
FR-F820-00770(18.5K)
22
FR-F820-00930(22K)
30
FR-F820-01250(30K)
37
FR-F820-01540(37K)
45
FR-F820-01870(45K)
55
FR-F820-02330(55K)
75
FR-F820-03160(75K)
90
FR-F820-03800(90K)
110
FR-F820-04750(110K)
NOTE
• Select an MCCB according to the power supply capacity.
• Install one MCCB per inverter. For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the
Instruction Manual (Startup) or Instruction Manual (Hardware) to select an appropriate fuse or MCCB.
MCCB
MCCB
26
2. INSTALLATION AND WIRING
2.1 Peripheral devices
Molded case circuit breaker (MCCB) / earth
leakage circuit breaker (ELB) (type NF or NV)
Power factor improving AC/DC reactor
Not installed
10 A
15 A
20 A
30 A
50 A
60 A
75 A
125 A
150 A
175 A
225 A
250 A
300 A
400 A
INV
M
INV
M
page
88.)
Magnetic contactor (MC) for installation
Power factor improving AC/DC reactor
Installed
10 A
S-T10
15 A
S-T10
15 A
S-T10
30 A
S-T21
40 A
S-T25
50 A
S-T35
75 A
S-T35
100 A
S-T50
125 A
S-T65
125 A
S-T100
150 A
S-T100
200 A
S-N150
225 A
S-N180
300 A
S-N220
400 A
400 A
500 A
on the inverter input side
Not installed
Installed
S-T10
S-T10
S-T10
S-T10
S-T21
S-T25
S-T35
S-T50
S-T50
S-T65
S-T100
S-N125
S-N150
S-N180
S-N300
S-N300
S-N400