Procedure for verifying parameters in the USB memory
Operating procedure
1.
Copy the parameter settings of the verification source inverter to the USB memory according to the procedure on
page
556.
2.
Move the USB memory device to the inverter to be verified.
3.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
4.
USB memory mode
Press
5.
Displaying the file selection screen
Press
6.
Selecting the file number
Turn
7.
Parameter verification
Turn
"
Press
the verification destination inverter. (It takes about 15 seconds to verify all the settings. During verification,
"
● If there are different parameters, the different parameter number and "
● To continue verification, press
8.
The verified file number and "
NOTE
• When "
558
5. PARAMETERS
5.16 Copying and verifying parameters using a USB memory
to change to the USB memory mode.
three times to display "
to select the file number to be verified, and press
to display the setting "
" appears.
to start verification of the parameter settings copied to the USB memory and the parameter settings of
" blinks.)
" blinks, the set frequency may be incorrect. To continue verification, press
" (file selection screen).
.
" (Parameter copy verification mode), and press
.
" are displayed alternately after verification ends.
" are displayed alternately.
.
.