○: Trigger enabled, ×: Trigger disabled
Pr.1471
Decimal
Binary
15
1111
14
1110
13
1101
12
1100
11
1011
10
1010
9
1001
8
1000
• Turning ON of the X98 signal can be used as a trigger to start the cleaning operation. For the X98 signal input, set "98" in
any of Pr.178 to Pr.189 to assign the function.
• When using the cleaning function for the purpose of periodic maintenance in such applications that require continuous
pump operation for a long time, use a time trigger. The time trigger is enabled by setting a time period before starting the
cleaning operation in Pr.1479 Cleaning time trigger. The timer starts when the timer starting condition is satisfied, and
the cleaning operation is performed at a time interval set in Pr.1479.
• Starting conditions of the timer for a time trigger
When the start command turns ON
When the cleaning ends
STF
Y215
Output
frequency
0 Hz
 Cleaning operation by the cleaning signal (X97 signal)
• When X97 signal is assigned to an input terminal, the cleaning operation can be finished when the cleaning signal (X97)
is turned from ON to OFF.
• For the X97 signal input, set "97" in any of Pr.178 to Pr.189 to assign the function.
Pr.1470 setting
0
Other than 0
400
5. PARAMETERS
5.11 (A) Application parameters
bit 3
bit 2
bit 1
×
×
×
×
×
×
×
×
ON
Start command ON trigger
ON
Pr.1479
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
X97 signal
Assignment
ON/OFF
Optional
Optional
Not assigned
OFF
Assigned
ON
Pr.1471
bit 0
Decimal
Binary
7
0111
×
6
0110
5
0101
×
4
0100
3
0011
×
2
0010
1
0001
×
0
0000
Time trigger
ON
Pr.1479
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
Cleaning operation
Disabled
Enabled
Disabled
Enabled
bit 3
bit 2
bit 1
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Time trigger
ON
Cleaning
Normal
operation
operation
(Pr.1470 = Once)
Cleaning end condition
After cleaning is performed for the
number of times set in Pr.1470.
• After cleaning is performed for the
number of times set in Pr.1470.
• When X97 signal turns OFF.
bit 0
×
×
×
×
Time