Mitsubishi Electric FR-F820-00046 Instruction Manual page 62

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

 Communication
Terminal
Type
Terminal name
symbol
PU connector
TXD+
Inverter transmission
terminal
TXD-
RXD+
Inverter reception
terminal
RXD-
GND
Earthing (grounding)
(SG)
USB A connector
USB B connector
 Safety stop signal
Terminal
Terminal name
symbol
Safety stop input
S1
(Channel 1)
Safety stop input
S2
(Channel 2)
Safety stop input
SIC
terminal common
Safety monitor
So (SO)
output (open
collector output)
Safety monitor
SOC
output terminal
common
RS-485 communication can be made through the PU connector (for connection
on a 1:1 basis only).
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Transmission speed: 4800 to 115200 bps
Wiring length: 500 m
RS-485 communication can be made through the RS-485 terminals.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Transmission speed: 300 to 115200 bps
Overall length: 500 m
A connector (receptacle). Plug a USB memory
device into this connector to copy parameter
settings or use the trace function.
Mini B connector (receptacle). By connecting
the inverter to a personal computer via this
connector, FR Configurator2 installed on the
computer can be used for setting the inverter, or
monitoring or testing the inverter operation.
Terminal function description
Use terminals S1 and S2 to receive the safety stop signal input
from the safety relay module. Terminals S1 and S2 can be used
at a time (dual channel).
The Inverter judges the condition of the internal safety circuit from
the status (shorted/opened) between terminals S1 and SIC, or
between S2 and SIC. When the status is opened, the inverter
output is shut off.
In the initial status, terminal S1 and S2 are shorted with terminal
PC by shorting wires. Terminal SIC is shorted with terminal SD.
Remove the shorting wires and connect the safety relay module
when using the safety stop function.
Common terminal for terminals S1 and S2.
The output status varies depending on the input status of the
safety stop signals.
The output is in HIGH state during occurrence of the internal
safety circuit failure. The output is in LOW state otherwise.
(The open collector transistor is ON (conductive) in LOW state.
The transistor is OFF (not conductive) in HIGH state.)
Refer to the Safety Stop Function Instruction Manual if the output
becomes in HIGH state even though both terminals S1 and S2
are open. (Contact your sales representative for this manual.)
Common terminal for terminal So (SO).
Terminal function description
Interface: conforms to USB
1.1 (USB 2.0 full-speed
compatible)
Transmission speed: 12
Mbps
Rated specification
Input resistance: 4.7 kΩ,
input current: 4 to 6
mADC (with 24 VDC
input)
Permissible load: 24
VDC (27 VDC at
maximum), 0.1 A (The
voltage drop is 3.4 V at
maximum while the
signal is ON.)
2. INSTALLATION AND WIRING
1
Refer
to page
2
473
3
475
4
5
74
6
74
7
Refer to
page
8
9
10
70
61
2.6 Control circuit