Mitsubishi Electric FR-F820-00046 Instruction Manual page 518

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

• BINARY OUTPUT
Object Identifier
Object Name
0
Terminal RUN CMD C
1
Terminal SU CMD
2
Terminal IPF CMD
3
Terminal OL CMD
4
Terminal FU CMD
Terminal ABC1
5
CMD
Terminal ABC2
6
CMD
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.
*2
Available regardless of the operation mode, operation command source, and speed command source.
Present Value
*1
Access Type
Represents actual output of terminal RUN.
Available when Pr.190 RUN terminal function selection = "82 or 182".
Controls actual output of terminal SU.
C
Available when Pr.191 SU terminal function selection = "82 or 182".
Controls actual output of terminal IPF.
C
Available when Pr.192 IPF terminal function selection = "82 or 182".
Controls actual output of terminal OL.
C
Available when Pr.193 OL terminal function selection = "82 or 182".
Controls actual output of terminal FU.
C
Available when Pr.194 FU terminal function selection = "82 or 182".
Controls actual output of terminal ABC1.
C
Available when Pr.195 ABC1 terminal function selection = "82 or 182".
Controls actual output of terminal ABC2.
C
Available when Pr.196 ABC2 terminal function selection = "82 or 182".
Description
(0: Inactive, 1: Active)
5. PARAMETERS
5.12 (N) Communication operation parameters
1
*2
2
*2
3
*2
*2
4
*2
*2
5
*2
6
7
8
9
10
517