Mitsubishi Electric FR-F820-00046 Instruction Manual page 450

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

• When the rotation direction is detected, the following operation is performed according to Pr.78 Reverse rotation
prevention selection setting.
Pr.299 setting
9999 (initial value)
0
1
• By setting "3 or 13" in Pr.162, the restart can be made smoother with even less impact than when "0, 2, 10, or 12" is set
in Pr.162.
When the inverter is restarted with "3, 13" set in Pr.162, offline auto tuning is required. (For details on offline auto tuning
of Advanced magnetic flux vector control, refer to
page
454.)
V/F control, Advanced magnetic flux vector control
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
Inverter output
voltage E(V)
Speed
Coasting
detection
+
time (Pr.57)
time
* The output shut off timing differs
according to the load condition.
NOTE
• The rotation speed detection time (frequency search) changes according to the rotation speed of the motor. (maximum 1 s)
• When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent protective function (E.OC[]) is
sometimes activated and prevents the inverter from restarting.
• If two or more motors are connected to one inverter, this function operates abnormally. (The inverter does not restart
successfully.)
• Because a DC injection brake is applied instantaneously at speed detection during a restart, the speed might drop if the
moment of inertia (J) of the load is small.
• If reverse operation is detected when "1" (reverse rotation disabled) is set to Pr.78, operation decelerates by reverse rotation
and then changes to forward rotation when the start command is forward rotation. The inverter does not restart when the start
command is reverse rotation.
• When "3 or 13" is set to Pr.162, limit the wiring length to within 100 m.
0
×
page
*
Restart cushion
time (Pr.58 setting)
Acceleration time
at a restart
(Pr.611 setting)
Pr.78 setting
1
×
×
○: With rotation direction detection ×: Without rotation direction detection
366, and for details on offline auto tuning of V/F control, refer to
2
×
×
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
449