Advertisement

5.9.5

Frequency setting voltage (current) bias and gain

The magnitude (slope) of the output frequency can be set as desired in relation to the frequency setting signal (0 to 5 VDC, 0
to 10 VDC, or 4 to 20 mA). Use Pr.73 Analog input selection (Pr.267 Terminal 4 input selection) and the voltage/current
input selection switch to switch among input of 0 to 5 VDC, 0 to 10 V, and 4 to 20 mA. (Refer to
Pr.
Name
C2 (902)
Terminal 2 frequency setting
*1
bias frequency
T200
C3 (902)
Terminal 2 frequency setting
*1
bias
T201
125 (903)
Terminal 2 frequency setting
T202
gain frequency
*1
T022
C4 (903)
Terminal 2 frequency setting
*1
gain
T203
C5 (904)
Terminal 4 frequency setting
*1
bias frequency
T400
C6 (904)
Terminal 4 frequency setting
*1
bias
T401
126 (905)
Terminal 4 frequency setting
T402
gain frequency
*1
T042
C7 (905)
Terminal 4 frequency setting
*1
gain
T403
C12 (917)
Terminal 1 bias frequency
*1
(speed)
T100
C13 (917)
Terminal 1 bias (speed)
*1
T101
C14 (918)
Terminal 1 gain frequency
*1
(speed)
T102
C15 (918)
Terminal 1 gain (speed)
*1
T103
241
Analog input display unit
M043
switchover
*1
The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
 Relationship between the analog input terminal function and the
calibration parameter
• Calibration parameter according to the terminal 1 function
Pr.868
Terminal function
setting
0 (initial
Auxiliary Frequency (speed)
value)
setting
Stall prevention operation
4
*1
level
9999
No function
Initial value
Setting
range
FM
CA
0 Hz
0 to 590 Hz Set the bias frequency for the terminal 2 input.
0%
0 to 300%
60 Hz 50 Hz 0 to 590 Hz Set the gain (maximum) frequency for the terminal 2 input.
100%
0 to 300%
0 Hz
0 to 590 Hz Set the bias frequency for the terminal 4 input.
20%
0 to 300%
60 Hz 50 Hz 0 to 590 Hz Set the gain (maximum) frequency for the terminal 4 input.
100%
0 to 300%
0 Hz
0 to 590 Hz
0%
0 to 300%
60 Hz 50 Hz 0 to 590 Hz
100%
0 to 300%
0
0
1
Bias setting
C2 (Pr.902) Terminal 2 frequency setting
bias frequency
C3 (Pr.902) Terminal 2 frequency setting
bias
C5 (Pr.904) Terminal 4 frequency setting
bias frequency
C6 (Pr.904) Terminal 4 frequency setting
bias
C16 (Pr.919) Terminal 1 bias command
(torque)
C17 (Pr.919) Terminal 1 bias (torque)
Description
Set the converted % of the bias voltage (current) for the terminal
2 input.
Set the converted % of the gain voltage (current) for the terminal
2 input.
Set the converted % of the bias current (voltage) for the terminal
4 input.
Set the converted % of the gain current (voltage) for the terminal
4 input.
Set the bias frequency (speed) for the terminal 1 input. (Speed
limit)
Set the converted % of the bias voltage for the terminal 1 input.
(Speed limit)
Set the gain (maximum) frequency (speed) for the terminal 1
input. (Speed limit)
Set the converted % of the gain voltage for the terminal 1 input.
(Speed limit)
% display
Select the unit for analog input display.
V/mA display
Calibration parameter
Pr.125 Terminal 2 frequency setting gain
frequency
C4 (Pr.903) Terminal 2 frequency setting gain
Pr.126 Terminal 4 frequency setting gain
frequency
C7 (Pr.905) Terminal 4 frequency setting gain
C18 (Pr.920) Terminal 1 gain command
(torque)
C19 (Pr.920) Terminal 1 gain (torque)
5.9 (T) Multi-function input terminal parameters
page
330.)
Gain setting
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
339