2.8.5
Connection of the power regeneration common
converter (FR-CV)
When wiring for connecting the power regeneration common converter (FR-CV) to the inverter, make sure to match the terminal
symbols (P/+, N/-) on the inverter and on the power regeneration common converter.
The FR-CV is compatible with the FR-F820-02330(55K) or lower and the FR-F840-01160(55K) or lower.
After making sure that the wiring is correct and secure, set "2" in Pr.30 Regenerative function selection. (Refer to
MCCB
Three-phase
AC power
supply
*1
Remove jumpers across terminals R/L1 and R1/L11 as well as across terminals S/L2 and S1/L21, and connect the power supply for the control
circuit to terminals R1/L11 and S1/L21. Do not connect anything to power input terminals (R/L1, S/L2, and T/L3). Incorrect connection will damage
the inverter. (The E.OPT fault (Option fault) occurs. (Refer to
*2
Terminal P3 is equipped in the FR-F820-00770(18.5K) to 01250(30K), and FR-F840-00470(22K) to 01800(75K). When connecting multiple
inverters in parallel, always use either terminal P/+ or P3 for the connection. (Do not use terminals P/+ and P3 together.)
*3
Do not install an MCCB across terminals P/+ and N/- (between terminals P/L+ and P/+ or between N/L- and N/-). Connecting the opposite polarity
of terminals N/- and P/+ will damage the inverter.
*4
Use Pr.178 to Pr.189 (Input terminal function selection) to assign the terminals used for the X10 signal. (Refer to
*5
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter without connecting them will damage the
power regeneration common converter.
*6
Always connect terminal RDY on the FR-HC2 to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect
terminal SE on the FR-HC2 to terminal SD on the inverter. Not connecting these terminals may damage the FR-CV.
NOTE
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must
be matched.
• Use the sink logic when the FR-CV is connected. It cannot be connected when the source logic is selected.
• Do not connect a DC reactor (FR-HEL) to the inverter when the FR-CV is connected.
80
2. INSTALLATION AND WIRING
2.8 Connection of stand-alone option units
Dedicated stand-alone
reactor (FR-CVL)
MC1
R/L11
R2/L12
S/L21
S2/L22
T/L31
T2/L32
FR-CV type
Power regeneration
common converter
R2/L1
S2/L2
P/L+
T2/L3
N/L-
P24
R/L11
SD
S/L21
∗5
RDYA
T/MC1
RDYB
RSO
SE
page
579.))
page
R/L1
U
∗1
S/L2
V
T/L3
W
R1/L11
S1/L21
Inverter
P/+ (P3)
∗2
∗3
N/-
PC
SD
∗6
X10
∗4
RES
page
355.)
539.)
M