Pid Control Enhanced Functions - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

5.11.11 PID control enhanced functions

PID control enhanced functions can be used to perform PID control according to applications.
Pr.
Name
1361
Detection time for PID output
A440
hold
1362
PID output hold range
A441
1363
PID priming time
A447
1364
Stirring time during sleep
A448
1365
Stirring interval time
A449
1366
Sleep boost level
A627
1367
Sleep boost waiting time
A628
1368
Output interruption cancel time
A629
111
Check valve deceleration time
F031
1369
Check valve closing completion
A446
frequency
1370
Detection time for PID limiting
A442
operation
1371
PID upper/lower limit pre-
A443
warning level range
1372
PID measured value control set
A444
point change amount
1373
PID measured value control set
A445
point change rate
1374
Auxiliary pressure pump
A450
operation starting level
1375
Auxiliary pressure pump
A451
operation stopping level
1377
PID input pressure selection
A452
1378
PID input pressure warning
A453
level
1379
PID input pressure fault level
A454
1380
PID input pressure warning set
A455
point change amount
1381
PID input pressure fault
A456
operation selection
 PID output hold (Pr.1361 and Pr.1362)
• The manipulated amount (PID output) can be fixed when the fluctuation of the deviation is small. This function eliminates
unnecessary acceleration/deceleration, which is effective to reduce the power consumption.
• When the deviation falls within the Pr.1362 PID output hold range and the elapsed time exceeds the Pr.1361 Detection
time for PID output hold, the manipulated amount (PID output) is fixed at the output frequency at that time.
Initial
Setting range
value
Set the time from when the deviation falls within the PID output hold
5 s
0 to 900 s
range until the PID output is held.
0 to 50%
Set the range in which the PID output is held.
9999
9999
The PID output holding is disabled.
Set the time from when the priming operation starts until the main
0 to 360 s
pump starts.
9999
9999
The PID priming pump function is disabled.
15 s
0 to 3600 s
Set the stirring time.
0 h
0 to 1000 h
Set the interval time for the stirring operation.
Increase the set point before the PID output suspension function is
0 to 100%
activated.
9999
9999
The PID sleep boost function is disabled.
0 s
0 to 360 s
Set the waiting time for the sleep boost operation.
Set the time from when the deviation reaches the output interruption
0 s
0 to 360 s
cancel level until the output is started.
0 to 3600 s
Set the deceleration time for the check valve deceleration function.
9999
9999
The check valve deceleration function is disabled.
0 to 120Hz
Set the frequency at which the check valve deceleration stops.
9999
9999
The check valve deceleration function is disabled.
Set the time from when the measured value reaches the pre-warning
0 s
0 to 900 s
level (P.1371) until the set point change is started.
Set the operation range for the PID upper/lower limit pre-warning
0 to 50%
function.
9999
9999
The PID upper/lower limit pre-warning function is disabled.
Set the set point change amount for the PID upper/lower limit pre-
5%
0 to 50%
warning operation.
Set the set point change rate for the PID upper/lower limit pre-
0%
0 to 100%
warning operation.
1000%
900 to 1100%
Set the deviation level for operating the auxiliary pressure pump.
1000%
900 to 1100%
Set the deviation level for stopping the auxiliary pressure pump.
1
Terminal 1 pressure input
2
Terminal 2 pressure input
9999
3
Terminal 4 pressure input
9999
The PID input pressure control function is disabled.
20%
0 to 100%
Set the input pressure warning level.
0 to 100%
Set the input pressure fault level.
9999
9999
The input pressure fault detection is disabled.
Set the set point change amount when the pressure reaches the
5%
0 to 100%
input pressure warning level.
The protective function (E.PID) for the input pressure fault is
0
activated.
0
A deceleration stop is performed when the input pressure fault
1
occurs.
Description
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
439

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents