5.4.17 Extended parameter display and user group
function
This function restricts the parameters that are read by the operation panel and parameter unit.
Pr.
Name
160
User group read
E440
selection
172
User group registered
E441
display/batch clear
173
User group registration
E442
174
User group clear
E443
*1
The read value is always "9999".
 Display of simple mode parameters and extended parameters (Pr.160)
• When Pr.160 = "9999", only the simple mode parameters are displayed on the operation panel (FR-DU08) and parameter
unit (FR-PU07). (For the simple mode parameters, refer to the parameter list on
• With the initial value (Pr.160 = "0", simple mode parameters and extended parameters can be displayed.
NOTE
• When a plug-in option in installed on the inverter, the option parameters can also be read.
• Every parameter can be read regardless of the Pr.160 setting when reading parameters via a communication option.
• When reading the parameters using the RS-485 terminals, all parameters can be read regardless of the Pr.160 setting by
setting Pr.550 NET mode operation command source selection and Pr.551 PU mode operation command source
selection.
1 (RS-485)
2 (PU), 3 (USB), 9999
(Automatic determination)
(initial value)
• When the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07) is installed, Pr.15 Jog frequency, Pr.16 Jog
acceleration/deceleration time, C42(Pr.934) PID display bias coefficient, C43(Pr.934) PID display bias analog value,
C44(Pr.935) PID display gain coefficient, C45(Pr.935) PID display gain analog value, and Pr.991 PU contrast
adjustment are displayed as simple mode parameters.
 User group function (Pr.160, Pr.172 to Pr.174)
• The user group function is a function for displaying only the parameters required for a setting.
• A maximum of 16 parameters from any of the parameters can be registered in a user group. When Pr.160 = "1", reading/
writing is enabled only for the parameters registered in user groups. (Parameters not registered in user groups can no
longer be read.)
• To register a parameter in a user group, set the parameter number in Pr.173.
• To clear a parameter from a user group, set the parameter number in Pr.174. To batch clear all the registered parameters,
set Pr.172 = "9999".
204
5. PARAMETERS
5.4 (E) Environment setting parameters
Initial value
FM
CA
9999
0
0
*1
9999
*1
9999
Pr.551
0 (Communication option)
1 (RS-485)
9999 (Automatic determination)
(initial value)
Setting range
9999
Only simple mode parameters are displayed.
0
Displays simple mode and extended parameters.
1
Only parameters registered in user groups are displayed.
Displays the number of parameters that are registered in
(0 to 16)
the user groups. (Read-only)
9999
Batch clear of user group registrations
0 to 1999, 9999
Sets the parameter number to register for the user group.
0 to 1999, 9999
Sets the parameter number to clear from the user group.
Pr.550
Pr.160 enabled/disabled
Enabled
Enabled
Disabled (All can be read)
With communication option: Enabled
Without communication option: Disabled
(All can be read)
Description
page
132.)