Mitsubishi Electric FR-F820-00046 Instruction Manual page 520

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

• System environment variables
Register
Definition
40010
Operation mode / inverter setting
[Operation mode / inverter setting]
Mode
Read value
EXT
H0000
PU
H0001
EXT
H0002
JOG
PU
H0003
JOG
NET
H0004
PU + EXT
H0005
*1
Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to
Restrictions in each operation mode conform with the computer link specification.
• Real time monitor
The register numbers and the monitor items are the same as those of the MODBUS RTU real time monitor. Refer to the
MODBUS RTU real time monitor on
• Parameter
Pr.
Register
0 to 999
41000 to 41999
C2 (902)
41902
42092
C3 (902)
43902
125 (903)
41903
42093
C4 (903)
43903
C5 (904)
41904
42094
C6 (904)
43904
126 (905)
41905
42095
C7 (905)
43905
C12 (917)
41917
42107
C13 (917)
43917
C14 (918)
41918
42108
C15 (918)
43918
C16 (919)
41919
42109
C17 (919)
43919
Read/write
Read/write
Write value
*1
H0010
*1
H0011
H0014
page
288.
Name
For details on parameter names,
refer to the parameter list
(page
132).
Terminal 2 frequency setting bias
(frequency)
Terminal 2 frequency setting bias
(analog value)
Terminal 2 frequency setting bias
(terminal analog value)
Terminal 2 frequency setting gain
(frequency)
Terminal 2 frequency setting gain
(analog value)
Terminal 2 frequency setting gain
(terminal analog value)
Terminal 4 frequency setting bias
(frequency)
Terminal 4 frequency setting bias
(analog value)
Terminal 4 frequency setting bias
(terminal analog value)
Terminal 4 frequency setting gain
(frequency)
Terminal 4 frequency setting gain
(analog value)
Terminal 4 frequency setting gain
(terminal analog value)
Terminal 1 bias frequency (speed) Read/write
Terminal 1 bias (speed)
Terminal 1 bias (speed) (terminal
analog value)
Terminal 1 gain frequency (speed) Read/write
Terminal 1 gain (speed)
Terminal 1 gain (speed) (terminal
analog value)
Terminal 1 bias command (torque) Read/write
Terminal 1 bias (torque)
Terminal 1 bias (torque)
(terminal analog value)
Remarks
The data is written as an operation mode setting for writing.
The data is read as the operation mode status for reading.
page
237.
Read/write
The parameter number + +41000 is the
Read/write
register number.
Read/write
Read/write
Analog value (%) set in C3 (902)
Analog value (%) of the voltage (current)
Read
applied to terminal 2
Read/write
Read/write
Analog value (%) set in C4 (903)
Analog value (%) of the voltage (current)
Read
applied to terminal 2
Read/write
Read/write
Analog value (%) set in C6 (904)
Analog value (%) of the current (voltage)
Read
applied to terminal 4
Read/write
Read/write
Analog value (%) set in C7 (905)
Analog value (%) of the current (voltage)
Read
applied to terminal 4
Read/write
Analog value (%) set in C13 (917)
Analog value (%) of voltage applied to
Read
terminal 1
Read/write
Analog value (%) set in C15 (918)
Analog value (%) of voltage applied to
Read
terminal 1
Read/write
Analog value (%) set in C17 (919)
Analog value (%) of voltage applied to
Read
terminal 1
5.12 (N) Communication operation parameters
1
2
3
4
5
6
7
Remarks
8
9
10
519
5. PARAMETERS