Mitsubishi Electric FR-F820-00046 Instruction Manual page 503

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

 Example) Read the register values of 41004 (Pr.4) to 41006 (Pr.6) from slave address 17 (H11).
Query message
Slave address
H11
(8 bits)
Normal response (Response message)
Slave address
Function
H11
H03
(8 bits)
(8 bits)
Read value
Register 41004 (Pr.4): H1770 (60.00 Hz)
Register 41005 (Pr.5): H0BB8 (30.00 Hz)
Register 41006 (Pr.6): H03E8 (10.00 Hz)
 Preset single register (writing data to holding registers) (H06 or 06)
• The content of the system environmental variables and inverter parameters (refer to
register area can be written.
• Query message
a. Slave address
(8 bits)
• Normal response (Response message)
a. Slave address
(8 bits)
• Query message setting
Message
a
Slave address
b
Function
c
Register address
d
Preset Data
• Content of normal response
The contents in the normal response (a to d, including the CRC check) are the same as those in the query messages.
In the case of broadcast communication, no response is returned.
 Example) Write 60 Hz (H1770) to 40014 (running frequency RAM) of slave address 5 (H05).
Query message
Slave address
H05
(8 bits)
Normal response (Response message)
The same data as those in the query message
NOTE
• With broadcast communication, no response is generated even if a query is executed, so when the next query is made, it must
be made after waiting for the inverter data processing time after the previous query is executed.
 Diagnostics (diagnosis of functions) (H08 or 08)
• A communication check can be made since the query message is sent and the query message is returned as it is as the
return message (subfunction code H00 function). Subfunction code H00 (Return query data)
502
5. PARAMETERS
5.12 (N) Communication operation parameters
Function
Starting address
H03
H03
(8 bits)
(8 bits)
Byte count
H06
H17
(8 bits)
(8 bits)
b. Function
c. Register address
H06
H
(8 bits)
(8 bits)
b. Function
c. Register address
H06
H
(8 bits)
(8 bits)
Set the address to send messages to. Setting "0" enables broadcast communication.
Set H06.
Set the holding register address to write data to.
Register address = holding register address (decimal) - 40001
For example, when register address 0001 is set, data is written to holding register address 40002.
Set the data to write to the holding register. Write data is fixed at 2 bytes.
Function
Register address
H06
H00
(8 bits)
(8 bits)
No. of points
HEB
H00
(8 bits)
(8 bits)
Data
H70
H0B
HB8
(8 bits)
(8 bits)
(8 bits)
d. Preset data
L
H
(8 bits)
(8 bits)
d. Preset data
L
H
(8 bits)
(8 bits)
Description
Preset data
H0D
H17
(8 bits)
(8 bits)
CRC check
H03
H77
(8 bits)
(8 bits)
CRC check
H03
HE8
H2C
(8 bits)
(8 bits)
(8 bits)
page
505) assigned to the holding
CRC check
L
L
(8 bits)
(8 bits)
CRC check
L
L
(8 bits)
(8 bits)
CRC check
H70
H17
(8 bits)
(8 bits)
H2B
(8 bits)
HE6
(8 bits)
H
(8 bits)
H
(8 bits)
H99
(8 bits)