Adjustment Of Terminal Fm/Ca And Terminal Am - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

*1
"HIGH" indicates when the open collector output transistor is OFF.
Item
Output method
Voltage between collector-emitter
Maximum permissible load current
Output pulse rate
Output resolution
*1
50k pulses/s when the monitor output value is 100%.
NOTE
• Terminal JOG input specifications (pulse train input or contact input) can be selected with Pr.291. When changing the setting
value, be careful not to change the terminal JOG input specifications. (Refer to
• Install a meter between terminals FM and SD after changing the Pr.291 setting value. During output the pulse train via terminal
FM (voltage output), be careful that voltage is not added to terminal FM.
• The meter cannot be used for the pulse input in a source logic type.
• If the All parameter clear is performed when the high-speed pulse train output is selected (Pr.291 = "10, 11, 20, 21, or 100"),
the output via terminal FM is changed from high-speed pulse train output to the voltage output because the Pr.291 setting
resets to the initial value "0". To perform the All parameter clear, remove the device connected to terminal FM first.
Open collector output circuit
5.8.4

Adjustment of terminal FM/CA and terminal AM

The output via terminal FM/CA or terminal AM corresponding to the full-scale value of a meter can be adjusted (calibrated) on
the operation panel or the parameter unit.
Pr.
C0
(900)
FM/CA terminal calibration
*1
M310
C1 (901)
AM terminal calibration
*1
M320
C8 (930)
Current output bias signal
*1
M330
C9 (930)
Current output bias current 0%
*1
M331
C10 (931)
Current output gain signal
*1
M332
C11 (931)
Current output gain current 100%
*1
M333
867
AM output filter
M321
869
Current output filter
M334
*1
The parameter number in parentheses is that used (displayed) on the LCD operation panel and the parameter unit.
 Terminal FM calibration (C0 (Pr.900))
• The output via terminal FM is set to the pulse output. By setting C0 (Pr.900), the meter connected to the inverter can be
calibrated by parameter setting without use of a calibration resistor.
302
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
High-speed pulse train output
specifications
NPN open collector output
30 V (max.)
80 mA
*1
0 to 55k pulses/s
3 pulses/s (excluding jitter)
FM output circuit
3.3kΩ
Pr.291
0, 1
8.2V
10, 11,
20, 21, 100
Name
Initial value Setting range
0%
100%
0.01 s
0.01 s
Terminal FM
Calibrates the scale of the meter connected to terminals FM and
CA.
Calibrates the scale of the analog meter connected to terminal
AM.
0 to 100%
Set the signal value at the minimum analog current output.
0 to 100%
Set the current value at the minimum analog current output.
Sets the signal value when the analog current output is at
0 to 100%
maximum.
0 to 100%
Set the current value at the maximum analog current output.
0 to 5 s
Set a filter for output via terminal AM.
0 to 5 s
Set a filter for output via terminal CA.
page 245
for pulse train input.)
Description