APPENDIX provides the reference information for use of this product.
Refer to APPENDIX as required.
9.1
For customers replacing the conventional model
with this inverter
9.1.1
Replacement of the FR-F700(P) series
 Differences and compatibility with the FR-F700(P) series
Item
Control method
Added functions
Maximum output
frequency
V/F control
PID control
Automatic restart after
instantaneous power
failure
PTC thermistor input
USB connector
Main circuit terminal
screw size
Control circuit terminal
block
Terminal response level
PU
Plug-in option
Plug-in option
connector
Communication option
Installation size
634
9. APPENDIX

9.1 For customers replacing the conventional model with this inverter

FR-F700(P)
V/F control
Simple magnetic flux vector control
IPM motor control
400 Hz
Turn the X14 signal ON to enable PID control.
Turn the CS signal ON to enable restart.
Pr.186 CS terminal function selection initial value:
"6"
Input from the terminal AU
(The function of terminal AU is switched by a switch.)
None
Terminals R/L1, S/L2, T/L3, U, V, and W: Same for all capacities
Terminals P/+, N/-, and P1: Same except for the 400 V class 01800(75K) (FR-F740(P)-01800(75K): M10,
FRF840-01800(75K): M8)
Screws for earthing (grounding): Same except for the 200 V class 03160(75K) (FR-F720(P)-03160(75K): M10,
FR-F820-03160(75K): M8)
Removable terminal block (screw type)
The FR-F800's I/O terminals have better response level than the FR-F700(P)'s terminals. By setting Pr.289
Inverter output terminal filter and Pr.699 Input terminal filter, the terminal response level can be compatible
with that of FR-F700(P). Set to approximately 5 to 8 ms and adjust the setting according to the system.
FR-DU07 (4-digit LED)
FR-PU07
Dedicated plug-in options (not interchangeable)
One connector (FR-F700P, FR-F700-CHT)
Two connectors (FR-F700-NA/EC)
Connected to the connector 1. (FR-F700P, FRF700-
CHT)
Connected to the connector 2. (FR-F700-NA/EC)
For standard models, installation size is compatible. (Replacement between the same capacities does not require
new mounting holes. However, for the 200 V class 03160(75K), the installation interchange attachment (FR-
F8AT) is required.)
For separated converter types, installation size is not compatible. (New mounting holes are required.)
FR-F800
V/F control,
Advanced magnetic flux vector control
PM motor control (IPM motor / SPM motor)
USB host function
Safety stop function
etc.
590 Hz
When the X14 signal is not assigned, just set a value in
Pr.128 to enable PID control.
When the X14 signal is assigned, turn the X14 signal ON
while Pr.128 ≠ "0" to enable PID control.
The CS signal does not need to be assigned. (Restart is
enabled with the Pr.57 setting only.)
Pr.186 CS terminal function selection initial value:
"9999"
Input through terminal 2
(The function of terminal 2 is switched by the Pr.561
setting.)
USB host: A connector
USB device: mini B connector
Removable terminal block (spring clamp type)
FR-DU08 (5-digit LED)
FR-LU08 (LCD operation panel)
FR-PU07 (Some functions such as Parameter copy are
unavailable.)
The FR-DU07 is not supported.
Three connectors
Connected to the connector 1