• When the setting is changed to the continuous operation (Pr.573 = "1 or 4") after the input current loss, the frequency before
loss is regarded as 0 Hz.
 Fault output (Pr.573 = "2")
• When the analog current input becomes 2 mA or lower, the protective function E.LCI (4 mA input fault) is activated and the
output is shut off.
• The following is the operation example during PID control (reverse action) operation.
Output frequency
20mA
Set point (fixed)
Measured value
4mA
STF
LF signal
PID signal
ALM signal
 Fault output after deceleration to stop (Pr.573 = "3")
• When the analog current input becomes 2 mA or lower, the inverter output decelerates the motor to a stop, and then the
protective function E.LCI (4 mA input fault) is activated and the output is shut off.
• When the analog current input is restored during the deceleration, the motor is accelerated again and operates according
to the current input.
• The following is the operation example during PID control (reverse action) operation.
Output frequency
20mA
Set point (fixed)
Measured value
4mA
STF
LF signal
PID signal
ALM signal
352
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
E.LCI occurs
Input current
decrease
Return
3mA
2mA
Decelerates as the input current is lost
After deceleration stop, E.LCI occurs
Input current
decrease
Return
3mA
2mA
Time
Time