Mitsubishi Electric FR-F820-00046 Instruction Manual page 379

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (The motor
capacity must be 0.4 kW or higher.)
If a motor with substantially low rated current compared with the inverter rated current, however, is used, speed and torque
accuracies may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter
rated current.
• The maximum frequency under PM motor control is 400 Hz.
• The motor may rotate slightly even if offline auto tuning is performed without the motor rotating (Pr.96 Auto tuning setting/
status = "1 or 11"). (It does not affect the tuning performance.)
Fix the motor securely with a mechanical brake, or before tuning, make sure that it is safe even if the motor rotates.
(Caution is required especially in vertical lift applications.)
• Tuning may be disabled depending on the motor characteristics.
 Settings
• To perform tuning, set the following parameters about the motor.
First motor
Second
Pr.
motor Pr.
80
453
81
454
9
51
84
457
83
456
71
450
96
463
*1
Set Pr.71 Applied motor according to the motor to be used. According to the Pr.71 setting, the range of the motor constant parameter setting
values and units can be changed. (For other setting values of Pr.71, refer to
*2
Setting value for the MM-EFS (1500 r/min specification) or the MM-THE4.
*3
Setting value for the MM-EFS (3000 r/min specification).
IPM motor
SPM motor
NOTE
• Under PM motor control, tuning cannot be performed even when Pr.96 = "101". When the MM-EFS or MM-THE4 is set to the
applied motor, tuning cannot be performed even when Pr.96 = "1 or 101".
• For tuning accuracy improvement, set the following parameters when the motor constants are known in advance.
First motor
Second
Pr.
motor Pr.
702
743
707
744
724
745
725
746
*1
The setting is valid only when a value other than "9999" is set in both Pr.707 (Pr.744) and Pr.724 (Pr.745).
 Performing tuning
• Before performing tuning, check the monitor display of the operation panel or parameter unit if the inverter is in the state ready
for tuning. The motor starts by turning ON the start command while tuning is unavailable.
378
5. PARAMETERS
5.10 (C) Motor constant parameters
Name
Motor capacity
Number of motor poles
Electronic thermal O/L relay
Rated motor frequency
Rated motor voltage
Applied motor
Auto tuning setting/status
Motor
MM-EFS (1500 r/min specification) / MM-THE4
MM-EFS (3000 r/min specification)
Other than MM-EFS/MM-THE4
Name
Maximum motor frequency
Motor inertia (integer)
Motor inertia (exponent)
Motor protection current level
Setting for a PM motor other than
MM-EFS or MM-THE4
Motor capacity (kW)
Number of motor poles (2 to 12)
Rated motor current (A)
Rated motor frequency (Hz)
Rated motor voltage (V)
8090, 8093 (IPM motor)
*1
9090, 9093 (SPM motor)
1
page
362.)
Motor constant parameter
Ω, mH, and A unit setting
210
240
8090
9090
Setting for a PM motor other than MM-
EFS/MM-THE4
Maximum motor frequency (Hz)
*1
Motor inertia
Jm = Pr.707 × 10^(-Pr.724) (kg·m
Maximum current level of the motor (%)
Setting for MM-EFS or MM-THE4
Set by IPM parameter initialization
(Refer to page
page
175.)
Rated motor voltage (V) written on the
rating plate.
*1*2
210, 213
*1*3
240, 243
11
Pr.71 setting
Motor constant parameter
internal data setting
213 (214)
243 (244)
8093 (8094)
9093 (9094)
Setting for MM-EFS/MM-THE4
9999 (initial value)
9999 (initial value)
2
)
9999 (initial value)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents