F) Setting Of Acceleration/Deceleration Time And Acceleration/Deceleration Pattern; Setting The Acceleration And Deceleration Time - Mitsubishi Electric FR-F820-04750 Instruction Manual

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

Parameters
5.5.1

Setting the acceleration and deceleration time

The following parameters are used to set motor acceleration/deceleration time.
Set a larger value for a slower acceleration/deceleration, and a smaller value for a faster acceleration/
deceleration.
For the acceleration time at automatic restart after instantaneous power failure, refer to Pr. 611 "Ac-
celeration time at a restart" (page 5-409, page 5-417).
Pr.
20
F000
21
F001
16
F002
611
F003
7
F010
8
F011
44
F020
45
F021
147
F022
791
F070
792
F071
Initial value for the FR-F820-00340(7.5K) or lower and FR-F840-00170(7.5K) or lower.
Initial value for the FR-F820-00490(11K) or higher and FR-F840-00250(11K) and higher.
FR-F800

(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern

Name
Acceleration/deceleration
60 Hz
reference frequency
Acceleration/deceleration
time increments
Jog acceleration/
deceleration time
Acceleration time at a
restart
Acceleration time
Deceleration time
Second acceleration/
deceleration time
Second deceleration time
Acceleration/deceleration
time switching frequency
Acceleration time in low-
speed range
Deceleration time in low-
speed range
Initial value
Setting range
FM
CA
50 Hz
1 to 590 Hz
0
0
1
0.5 s
0 to 3600 s
9999
0 to 3600 s, 9999
5 s
0 to 3600 s
15 s
10 s
0 to 3600 s
30 s
5 s
0 to 3600 s
0 to 3600 s
9999
9999
0 to 590 Hz
9999
9999
0 to 3600 s
9999
9999
0 to 3600 s
9999
9999
Description
Set the frequency that will be the basis of
acceleration/deceleration time. As
acceleration/deceleration time, set the
frequency change time from a stop status
to Pr. 20.
Select the increment
Increment: 0.1 s
for the acceleration/
deceleration time
Increment: 0.01 s
setting and the
setting range.
Set the acceleration/deceleration time for
JOG operation (from stop status to Pr. 20).
Refer to page 5-139
Set the acceleration time for restart (from
stop status to Pr. 20).
When "9999" is set, standard acceleration
time (like Pr. 7) is applied as the
acceleration time at restart.
Refer to page 5-409, page 5-417.
Set the motor acceleration time (from
stop status to Pr. 20).
Set the motor deceleration time (from
Pr. 20 to stop status).
Set the acceleration/deceleration time
when the RT signal is ON.
Set the deceleration time when the RT
signal is ON.
Acceleration time = deceleration time
Set the frequency where the acceleration/
deceleration time switches to the time set
in Pr. 44 and Pr. 45.
No function
Set the acceleration time in a low-speed
range (less than 10% of the rated motor
frequency).
The acceleration time set in Pr. 7 is
applied. (While RT signal is ON, the second
function is enabled.)
Set the deceleration time in a low-speed
range (less than 10% of the rated motor
frequency).
The deceleration time set in Pr. 8 is
applied. (While RT signal is ON, the second
is enabled.)