Connection Of The Brake Unit (Fr-Bu) - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

2.8.2

Connection of the brake unit (FR-BU)

Connect the brake unit (FR-BU(-H)) as follows to improve the braking capability during deceleration. The FR-BU is compatible
with the FR-F820-02330(55K) or lower and the FR-F840-01160(55K) and lower.
Three-phase AC
power supply
*1
When wiring, make sure to match the terminal symbols (P/+, N/-) on the inverter and on the brake unit (FR-BU(-H)). (Incorrect connection will
damage the inverter.)
*2
When the power supply is 400 V class, install a stepdown transformer.
*3
The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) must be within 5 m. Even when the cable is twisted, the
wiring length must be within 10 m.
*4
Terminal P3 is equipped in the FR-F820-00770(18.5K) to 01250(30K) and the FR-F840-00470(22K) to 01800(75K). Terminal P3 has the same
function as terminal P\+ on the inverter.
NOTE
• If the transistors in the brake unit should become faulty, the resistor will overheat. Install a magnetic contactor on the inverter's
input side and configure a circuit that shut off the current in case of a fault.
• Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor (FR-HEL).
2.8.3
Connection of the brake unit (BU type)
Connect the brake unit (BU type) correctly as follows. Incorrect connection will damage the inverter. Remove the jumpers
across terminals HB and PC and terminals TB and HC on the brake unit, and fit one across terminals PC and TB. The The BU
type brake unit is compatible with the FR-F820-02330(55K) or lower and the FR-F840-01160(55K) or lower.
Three-phase
AC power
supply
*1
When the power supply is 400 V class, install a stepdown transformer.
*2
Terminal P3 is equipped in the FR-F820-00770(18.5K) to 01250(30K) and the FR-F840-00470(22K) to 01800(75K). Terminal P3 has the same
function as terminal P\+ on the inverter.
78
2. INSTALLATION AND WIRING
2.8 Connection of stand-alone option units
MCCB
MC
MCCB
∗2
T
MC
R/L1
U
S/L2
V
T/L3
W
Inverter
P/+ (P3)
∗4
N/-
10 m or less
T
∗1
Inverter
Motor
U
R/L1
V
M
S/L2
W
T/L3
N/-
∗2
P/+ (P3)
Discharging
resistor
ON
OFF
MC
MC
FR-BR
Motor
P
TH1
M
PR
TH2
FR-BU
PR
HA
P/+
HB
∗1
N/-
HC
∗3
ON
OFF
MC
MC
Brake unit
Remove the
(BU type)
jumper
TB
N
HC
OCR
HB
HA
OCR
PC
PR
Fit a jumper
P

Hide quick links:

Advertisement

Table of Contents
loading