Offline Auto Tuning - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

5.10.2 Offline auto tuning

Magnetic flux
Magnetic flux
Magnetic flux
The offline auto tuning enables the optimal operation of a motor.
• Under Advanced magnetic flux vector control, automatic measurement of motor constants (offline auto tuning) enables
optimal operation of motors even when motor constants vary, when a motor of another company is used, or when the wiring
distance is long.
For the offline auto tuning for a PM motor, refer to
Pr.
Name
684
Tuning data unit
C000
switchover
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor
C102
poles
9
Electronic
C103
thermal O/L relay
83
Rated motor
C104
voltage
84
Rated motor
C105
frequency
707
Motor inertia
C107
(integer)
724
Motor inertia
C108
(exponent)
96
Auto tuning
C110
setting/status
90
Motor constant
C120
(R1)
91
Motor constant
C121
(R2)
Motor constant
92
(L1)/d-axis
C122
inductance (Ld)
Motor constant
93
(L2)/q-axis
C123
inductance (Lq)
94
Motor constant
C124
(X)
82
Motor excitation
C125
current
Torque current/
859
Rated PM motor
C126
current
298
Frequency search
A711
gain
366
5. PARAMETERS
5.10 (C) Motor constant parameters
page
375.
Initial
Setting range
value
0
0
1
0 to 6, 13 to 16, 20, 23, 24,
40, 43, 44, 50, 53, 54, 70,
0
73, 74, 210, 213, 214, 240,
243, 244, 8090, 8093, 8094,
9090, 9093, 9094
*1
0.4 to 55 kW
9999
*2
0 to 3600 kW
9999
2, 4, 6, 8, 10, 12
9999
9999
Inverter
*1
0 to 500 A
rated
*2
0 to 3600 A
current
*3
0 to 1000 V
200/400 V
10 to 400 Hz
9999
9999
9999
10 to 999, 9999
9999
0 to 7, 9999
0
1
0
11
101
*4
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
*1*4
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
0 to 6000 mH, 9999
9999
0 to 400 mH, 9999
0 to 6000 mH, 9999
9999
0 to 400 mH, 9999
*4
9999
0 to 100%, 9999
*1*4
0 to 500 A, 9999
9999
0 to 3600 A, 9999
*1*4
0 to 500 A, 9999
9999
0 to 3600 A, 9999
0 to 32767
9999
9999
Internal data converted value
The value is indicated in A, Ω, mH, or %.
By selecting a motor, the thermal characteristic and motor
constant of each motor are set.
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Set the rated motor current.
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
The setting value of Pr.3 Base frequency is used.
Set the motor inertia.
9999: The constant value of Mitsubishi Electric motor (SF-JR,
SF-HR, SF-JRCA, or SF-HRCA and so on) is used.
No offline auto tuning
Offline auto tuning is performed without the motor rotating.
Offline auto tuning is performed without the motor rotating (V/F
control, IPM motor MM-EFS/MM-THE4). (Refer to
Offline auto tuning is performed with the motor rotating.
*2*4
*2*4
*1*4
*2*4
Tuning data
(The value measured by offline auto tuning is automatically
*1*4
set.)
*2*4
9999: The constant value of Mitsubishi Electric motor (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) is used.
*2*4
*2*4
The offline auto tuning automatically sets the gain required for
the frequency search.
The constant value of Mitsubishi Electric motor (SF-PR, SF-JR,
SF-HR, SF-JRCA, SF-HRCA and so on) is used.
Description
page
454.)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents