Mitsubishi Electric FR-F820-00046 Instruction Manual page 212

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

NOTE
• When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr.259 = "8"), or "measurement
error" (Pr.259 = "9") may occur, or the status may remain in "measurement start" (Pr.259 = "1"). To perform measurement,
first eliminate the following conditions. Under the following conditions, even if "measurement complete" (Pr.259 = "3") is
reached, measurement cannot be performed correctly.
-
FR-HC2, FR-CV, MT-RC, or a sine wave filter is connected.
-
Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.
-
The power supply is switched ON during measurement.
-
The motor is not connected to the inverter.
-
The motor is running (coasting).
-
The motor capacity is smaller than the inverter capacity by two ranks or more.
-
The inverter output is shut off or a fault occurred while the power was OFF.
-
The inverter output is shut off with the MRS signal.
-
The start command is given while measuring.
-
The applied motor setting is incorrect.
• Operation environment: Surrounding air temperature (annual average of 40°C (free from corrosive gas, flammable gas, oil
mist, dust and dirt)).
Output current: 80% of the inverter rating
• Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of the
magnetic contactor must be avoided.
WARNING
• When measuring the main circuit capacitor capacity (Pr.259 = "1"), the DC voltage is applied to the motor for about 1
second at power OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.
 Life display of the cooling fan
• If a cooling fan speed of less than the specified speed (refer below) is detected, the indication of the Fan alarm "
(FN) is displayed on the operation panel or the parameter unit. As an alert output, bit 2 of Pr.255 is turned ON (set to 1),
and the Y90 signal and Alarm (LF) signal are also output.
• For the terminal used for the LF signal, set "98" (positive logic) or "198" (negative logic) in any of Pr.190 to Pr.196 (Output
terminal function selection).
Capacity
FR-F820-00250(5.5K) or lower, FR-F820-03160(75K) or higher, FR-
F840-00126(5.5K) or lower
FR-F820-00340(7.5K) to FR-F820-02330(55K)
FR-F840-00170(7.5K) to FR-F840-03610(160K)
FR-F846-00023(0.75K) to FR-F846-03610(160K)
FR-F840-04320(185K) or higher, FR-F842-07700(355K) or higher
NOTE
• When the inverter is mounted with two or more cooling fans, "FN" is displayed even only one of the fans is detected.
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
• For replacement of each part, contact the nearest Mitsubishi FA center.
 Life display of internal air circulation fans (IP55 compatible models)
• IP55 compatible models are equipped with the internal air circulation fan inside the inverter other than the cooling fan. The
internal fan fault "
70% of the rated value for the internal air circulation fan. (FN is displayed on the parameter unit (FR-PU07).) As an alarm
display, Pr.255 bit 4 is turned ON and also a warning is output to the Y90 signal and Alarm (LF) signal.
• For the terminal used for the LF signal, set "98" (positive logic) or "198" (negative logic) in any of Pr.190 to Pr.196 (Output
terminal function selection).
" (FN2) appears on the operation panel (FR-DU08) when the rotations per minute is less than
Fan alarm output level
Less than 50% of the rated
rotations per minute
Less than 70% of the rated
rotations per minute
Less than 1700 r/min
5.4 (E) Environment setting parameters
1
2
3
4
5
6
7
8
9
"
10
211
5. PARAMETERS