Earthing (Grounding) Precautions - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

2.5.4

Earthing (grounding) precautions

Always earth (ground) the motor and inverter.
 Purpose of earthing (grounding)
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use.
An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture an
insulating material that can shut off a leakage current completely, and actually, a slight current flows into the case. The purpose
of earthing (grounding) the case of an electrical apparatus is to prevent operators from getting an electric shock from this
leakage current when touching it.
To avoid the influence of external noises, the earthing (grounding) is important to EMI-sensitive equipment that handle low-
level signals or operate very fast such as audio equipment, sensors, computers.
 Earthing (grounding) system to be established
As described previously, the purpose of earthing (grounding) is roughly classified into the electrical shock prevention and the
prevention of malfunction due to the influence of electromagnetic noise. These two purposes should be clearly distinguished,
and the appropriate earth (ground) system must be established to prevent the leakage current having the inverter's high
frequency components from reversing through another earth (ground) point for malfunction prevention by following these
instructions:
• Make the separate earth (ground) connection (I) for high frequency products such as the inverter from any other devices
(EMI-sensitive devices described above) wherever possible.
Establishing adequate common (single-point) earth (ground) system (II) shown in the following figure is allowed only in
cases where the separate earth (ground) system (I) is not feasible. Do not make inadequate common (single-point) earth
(ground) connection (III).
As leakage currents containing many high frequency components flows into the earthing (grounding) cables of the inverter
and peripheral devices (including a motor), the inverter must also be earthed (grounded) separately from EMI-sensitive
devices described above.
In a high building, it may be effective to use its iron structure frames as earthing (grounding) electrode for EMI prevention
in order to separate from the earth (ground) system for electric shock prevention.
- Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes
(NEC section 250, IEC 61140 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply
for 400 V class inverter in compliance with EN standard must be used.
- Use the thickest possible earthing (grounding) cable. The earthing (grounding) cable should be equal to the size
indicated in the table on
- The earthing (grounding) point should be as close as possible to the inverter, and the earth (ground) wire length should
be as short as possible.
- Run the earthing (grounding) cable as far away as possible from the I/O wiring of the EMI-sensitive devices and run
them in parallel in the minimum distance.
Other
Inverter
equipment
(I) Separate earthing (grounding): Good
NOTE
• To be compliant with the EU Directive (Low Voltage Directive), refer to the Instruction Manual (Startup).
page
50.
Inverter
(II) Common (single-point) earthing (grounding): OK
Other
equipment
(III) Inadequate common (single-point) earthing (grounding): Bad
Other
Inverter
equipment