• Input signal
Signal
Function
X14
PID control valid
X80
Second PID control valid
PDI1
PID multistage set point setting 1 38
PDI2
PID multistage set point setting 2 39
PDI3
PID multistage set point setting 3 40
PID forward/reverse action
X64
switchover
Second PID forward/reverse
X79
action switchover
X72
PID P control switchover
X73
Second PID P control switchover 73
• Output signal
Signal
Function
FUP
PID upper limit
Second PID upper
FUP2
limit
FDN
Lower limit output
Second PID lower
FDN2
limit
PID forward/reverse
RL
rotation output
Second PID forward/
RL2
reverse rotation
output
During PID control
PID
activated
Second During PID
PID2
control activated
PID output
SLEEP
interruption
During second PID
SLEEP2
output shutoff
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters after
confirming the function of each terminal.
 PID automatic switchover control (Pr.127)
• The system can be started up more quickly by starting up without PID control activated.
Pr.178 to
Pr.189
setting
14
When this signal is assigned to the input terminal, PID control is enabled
when this signal is ON.
80
The set point set in Pr.1460 to Pr.1466 can be selected by combining the
ON/OFF status of the signals.
64
PID control is switched between forward and reverse action without
changing parameters by turning ON this signal.
79
72
Integral and differential values can be reset by turning ON this signal.
Pr.190 to Pr.196
setting
Positive
Negative
logic
logic
15
115
Output when the measured value signal exceeds Pr.131 PID upper limit
(Pr.1143 Second PID upper limit).
201
301
14
114
Output when the measured value signal falls below Pr.132 PID lower limit
(Pr.1144 Second PID lower limit).
200
300
16
116
"Hi" is output when the output display of the parameter unit is forward rotation
(FWD) and "Low" is output when the display is reverse rotation (REV) and stop
(STOP).
202
302
Turns ON during PID control.
47
147
When the PID calculation result is not reflected to the output frequency
(Pr.128< "2000"), the PID signal turns OFF at turn OFF of the start signal.
When the PID calculation result is reflected to the output frequency (Pr.128 ≥
203
303
"2000"), the PID signal turns ON regardless of the start signal status during PID
calculation.
70
170
Set Pr.575 Output interruption detection time (Pr.1147 Second output
interruption detection time) ≠ "9999". This signal turns ON when the PID
output suspension function is activated.
204
304
Description
Description
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
9
10