5.4.21 Current average value monitor signal

The output current average value during constant-speed operation and the maintenance timer value are output to the Current
average monitor signal (Y93) signal as a pulse. The output pulse width can be used in a device such as the I/O unit of a
programmable controller as a guideline for the maintenance time for mechanical wear, belt stretching, or deterioration of
devices with age.
The pulse is repeatedly output during constant-speed operation in cycles of 20 seconds to the Current average value monitor
(Y93) signal.
Programmable controller
maintenance
time
parts have
reached their life
Pr.
Name
555
Current average time
E720
556
Data output mask time
E721
Current average value
557
monitor signal output
E722
reference current
*1
For the FR-F820-02330(55K) or lower, and FR-F840-01160(55K) or lower.
*2
For the FR-F820-03160(75K) or higher, and FR-F840-01800(75K) or higher.
 Operation example
• The pulse output of the Current average monitor signal (Y93) signal is indicated below.
• For the terminal used for the Y93 signal output, assign the function by setting "93 (positive logic)" or "193 (negative logic)"
in any of Pr.190 to Pr.194 (Output terminal function selection). (This cannot be assigned by setting in Pr.195 ABC1
terminal function selection or Pr.196 ABC2 terminal function selection.)
Y93 signal
Data output mask time
When the speed has changed to constant
from acceleration/deceleration, Y93 signal is
not output for Pr. 556 time.
Start pulse
Output as Hi pulse shape for 1 s (fixed)
The output currents are averaged during the time
period set in Pr.555.
Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9 s (10 to 180%) during start pulse output.
output current average value (A)
Signal output time=
Pr. 557 (A)
 Pr.556 Data output mask time setting
• Immediately after acceleration/deceleration is shifted to constant-speed operation, the output current is unstable
(transitional state). Set the time for not obtaining (masking) transitional state data in Pr.556.
selection)page 312
Output
Input
unit
unit
Inverter
Initial value
Setting range
1 s
0.1 to 1 s
0 s
0 to 20 s
0 to 500 A
Inverter rated
current
0 to 3600 A
From acceleration to constant speed operation
Output
frequency
1 cycle (20 s)
Maintenance timer pulse
The maintenance timer value (Pr. 503) is output
as Hi output pulse shape for 2 to 9 s (16000h to
72000h).
Signal output time=
5 s
Set the time for calculating the average current during start
pulse output (1 second).
Set the time for not obtaining (masking) transitional state
data.
*1
Set the reference (100%) for outputting the output current
average value signal.
*2
Time
Next cycle
End pulse
output as low pulse
shape for 1 to 16.5 s
Pr. 503
100h
5 s
40000h