Mitsubishi Electric FR-F820-00046 Instruction Manual page 94

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

 Equivalent capacity limit
Received power voltage
6.6 kV
22/33 kV
66 kV or more
 Harmonic content (when the fundamental current is considered as 100%)
Reactor
5th
Not used
65
Used (AC side)
38
Used (DC side)
30
Used (AC, DC sides)
28
 Calculation of equivalent capacity P0 of harmonic generating equipment
"Equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic generating
equipment and is calculated by the following equation. If the sum of equivalent capacities is higher than the limit (refer to the
list of the equivalent capacity limits), harmonics must be calculated by the equation in next subheading.
P0 = Σ (Ki × Pi) [kVA]
Ki: Conversion factor (Refer to the list of the conversion factors.)
Pi: Rated capacity of harmonic generating equipment
i: Number indicating the conversion circuit type
*1
Rated capacity: Determined by the capacity of the applied motor and found in the table "Rated capacities and outgoing harmonic currents of
inverter-driven motors". The rated capacity used here is used to calculate the generated harmonic amount and is different from the power supply
capacity required for actual inverter drive.
 Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage) × operation ratio ×
harmonic content
• Operation ratio: actual load factor × operation time ratio during 30 minutes
• Harmonic content: Refer to the list of the harmonic content.
 Rated capacities and outgoing harmonic currents of inverter-driven motors
Fundamental
Applicable
wave current (A)
motor (kW)
200 V
400 V
0.4
1.61
0.81
0.75
2.74
1.37
1.5
5.50
2.75
2.2
7.93
3.96
3.7
13.0
6.50
5.5
19.1
9.55
7.5
25.6
12.8
11
36.9
18.5
15
49.8
24.9
18.5
61.4
30.7
22
73.1
36.6
30
98.0
49.0
37
121
60.4
45
147
73.5
55
180
89.9
Reference capacity
50 kVA
300 kVA
2000 kVA
7th
11th
41
8.5
14.5
7.4
13
8.4
9.1
7.2
*1
[kVA]
Fundamental
Outgoing harmonic current converted from 6.6 kV (mA) (No reactor, 100%
Rated
wave current
capacity
converted from
(kVA)
5th
6.6 kV (mA)
49
0.57
31.85
83
0.97
53.95
167
1.95
108.6
240
2.81
156.0
394
4.61
257.1
579
6.77
376.1
776
9.07
504.4
1121
13.1
728.7
1509
17.6
980.9
1860
21.8
1209
2220
25.9
1443
2970
34.7
1931
3660
42.8
2379
4450
52.1
2893
5450
63.7
3543
13th
17th
7.7
4.3
3.1
3.4
3.2
1.9
5.0
4.7
3.2
4.1
3.2
2.4
operation ratio)
7th
11th
13th
20.09
4.165
3.773
34.03
7.055
6.391
68.47
14.20
12.86
98.40
20.40
18.48
161.5
33.49
30.34
237.4
49.22
44.58
318.2
65.96
59.75
459.6
95.29
86.32
618.7
128.3
116.2
762.6
158.1
143.2
910.2
188.7
170.9
1218
252.5
228.7
1501
311.1
281.8
1825
378.3
342.7
2235
463.3
419.7
3. PRECAUTIONS FOR USE OF THE INVERTER
19th
23rd
25th
2.6
1.8
1.7
1.3
3.0
2.2
1.6
1.4
17th
19th
23rd
25th
2.107
1.519
1.274
0.882
3.569
2.573
2.158
1.494
7.181
5.177
4.342
3.006
10.32
7.440
6.240
4.320
16.94
12.21
10.24
7.092
24.90
17.95
15.05
10.42
33.37
24.06
20.18
13.97
48.20
34.75
29.15
20.18
64.89
46.78
39.24
27.16
79.98
57.66
48.36
33.48
95.46
68.82
57.72
39.96
127.7
92.07
77.22
53.46
157.4
113.5
95.16
65.88
191.4
138.0
115.7
80.10
234.4
169.0
141.7
98.10
3.2 Power supply harmonics
1
2
3
4
5
6
7
8
9
10
93